Spec Sheet
AZ95H09EAC
GE Zoneline
®
Heat Pump Single Package
Vertical Air Conditioner 265 Volt
Specification Created 12/20
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
31-7/8″
23-5/8″
24-1/8″
POWER CONNECTION REQUIREMENTS (RESISTANCE HEAT)
265 VOLT 9,000/12,000 BTUh 18,000 BTUh
POWER
CONNECTION KIT
RAK515D RAK520D RAK530D RAK520D RAK530D
Heater Watts 2450 3450 5000 3450 5000
MCA 15 20 30 20 30
Recommend
Protective Device
(MOCP)
15 amp
time-delay
fuse or
breaker
20 amp
time-delay
fuse or
breaker
30 amp
time-delay
fuse or
breaker
20 amp
time-delay
fuse or
breaker
30 amp
time-delay
fuse or
breaker
*There is no 15 amp breaker option available for 18,000 BTUh models due to compliance with UL standard 60335-2-40
MINIMUM CLEARANCES:
FRONT-ACCESS CLOSETS
-Allow 3" in front of unit, Allow 3" on each side of unit.
SIDE-ACCESS CLOSETS
- Allow 5" in front of unit, Allow 3" on each side of unit.
REQUIRED COMPONENTS FOR INSTALLATION
- Drain Platform (RAVDPLAT)
- Plenum or Transition Plenum
- Exterior Grille
- Return Air Grille/ Access Panel
- Remote Thermostat
- Power Connection Kit
For answers to your Monogram, GE Café
™
, GE Profile
™
or GE Appliances
product questions, visit our website at geappliances.com or call
GE Answer Center
®
Service, 800.626.2000.
PERFORMANCE DATA
- Cooling Capacity – 8,700 BTUh
- EER – 11.0
- COP - 3.3