Data Manual
16
Some installations may want to govern the ability of the 
unit to operate from a control device remote to the unit or 
even remote to the room in which the unit is located. The 
general term given to systems such as this is Central Desk 
Control (CDC). The most common installation of this type 
of system is a switch mounted at the registration desk 
and, upon guest check-in, a button is pushed or a switch 
is moved to allow the air conditioner to operate. Likewise, 
when the guest checks out, the device is put into the 
“OFF” position so the unit will not operate while the room 
is vacant. 
It is not necessary that the controlling device be located  
at a central desk to employ a device that will control the  
unit operation. For instance, in some resort areas, devices  
are connected to sliding glass doors and opening the door 
causes a contact to close, turning the air conditioner off.  
This prevents energy being wasted by operating the air 
conditioner when warm, humid air is entering the room.  
Some systems operate by motion sensors or heat-sensing 
detectors mounted in the room. These types of systems 
determine occupant presence in the room and allow the  
unit to operate; if no one is in the room the device signals  
the air conditioner to turn off. 
There is a wide variety of devices available, each with  
its own benefits and constraints. While GE Appliances 
does not offer components that are external to the 
unit for a Central Desk Control system, GE Appliances 
Zoneline units are compatible with most CDC and energy 
management systems. 
All GE Zoneline AZ45 and AZ65 Series units are 
compatible with simple on/off 2-wire Central Desk Control 
(CDC) systems. Consult with the provider of the energy 
management system to be sure it is compatible with  
GE Zoneline units. 
All GE Zoneline units have a port available and offer 
accessory (RAKCDC) to provide an CDC interface to most 
of the energy management systems. 
Control power to the switch (24 VAC) is provided by 
the GE Zoneline unit. 
IMPORTANT CDC COMMENTS  
(ALL SERIES APPLICABLE)
1. When the switching device closes the circuit of the CDC 
conductors, the unit operation stops.
2. Do not use a common bus (at the unit or at the switch 
panel) in the wiring. Both wires comprising the circuit 
must connect to the unit connectors and to the 
controlling switch. Running one wire from one unit 
to another unit is common busing and may damage 
internal components or cause erratic operation of the 
system.
3. A 24-volt transformer is contained within the Zoneline 
unit. No external voltage may be applied to the unit 
through the CDC terminals. (Voltage on the CDC 
conductors is 24 volts AC.)
4. When the remote switch is closed, the unit cannot be 
operated in the fan, cool or heat modes. Recommended 
wire size must be followed as a minimum requirement.
Freeze Sentinel and Heat Sentinel remain operational  
when the unit is connected to a CDC system. Even if the 
unit is turned “OFF” at the central location, if the sensor 
at the unit detects the low or high limit temperature, the 
unit will automatically turn on until it reaches the preset 
shutdown temperature (46°F heating, 80°F cooling).
Connecting the Zoneline unit to a CDC system does 
not eliminate the ability to connect the unit to a remote 
thermostat. Once the circuit is “opened,” and control 
of the unit removed from the CDC system, the selected 
controls—either the unit-mounted control or the remote 
thermostat—govern the operation of the unit.
Please see page 55 for installation recommendations  
for the Central Desk Control wiring. 
CDC TERMINAL LOCATION AND TYPICAL WIRING 
See page 19 for location of CDC terminals on unit.
WIRE SIZE #AWG MAXIMUM ALLOWABLE LENGTH
#22 600 Ft.
#20 900 Ft.
#18 1,500 Ft.
#16 2,000 Ft.
CENTRAL DESK CONTROL
RAKCDC  
EXAMPLE OF COMMON BUSING
NOT PERMITTED
TYPICAL WIRING
(Wiring from RAKCDC connector to 
field devices is field supplied)
RAKCDC 
CONNECTOR
(sold separately)
FIELD SUPPLIED 
CDC SWITCH
INCORRECT COMMON BUSING
NORMALLY OPEN SWITCH= 
UNIT OPERATIONAL
POWER RED 
CDC BLUE
E. FAN YELLOW
ARCHITECTS & ENGINEERS DATA MANUAL AZ45/AZ65 SERIES










