Installation Guide
Electrical Connections (347/480V)
Optional Mounting Methods
1 2
Attach two rod mount brackets to xture using four
10-32 x 3/8” pan head screws per bracket.
Secure 1/2” threaded rods into structural members in
ceiling. Place a nut on each threaded rod where xture
should hang. Slide xture onto threaded rods and tighten
second nut onto rods to secure xture.
Rod Mount Kit
OPTION A
Attach to
structural member
Fasten with nuts
1
4
2
Loosen screws to remove endcap.
Using UL listed wire connectors, connect AC source green
to xture green (ground), and AC black and red to xture
black and red. Reattach endcap.
Option: power input from top – A) Install 1/2” conduit, or
B) install AC power cord with strain relief.
A) Conduit B) Power cord
3
Option: power input from side – Remove knockout in endcap
and A) Install 1/2” conduit, or B) install AC power cord with
strain relief. Plug unused hole on top with appropriate tting.
A) Conduit B) Power cord
0-10V Dimmer
Optional Installation: 0-10V Volt Dimming
Black
To AC Main
White
Green/Yellow
Violet
Grey
Blue/White
Black/White
Yellow
Line
Neutral
Ground
0-10V(+)
0-10V(-)
LED Driver
To 0-10V
Dimmer
Run wires from controller through a different
knockout than the AC input wire. At output side of
LED driver, make appropriate connections using
twist-on wire connectors. Follow lighting controller
installation instructions.
Note: Daisy chaining the 0-10V wires from xture
to xture for the 347-480V versions of ABHG is not
allowed.