Installation Guide
6
 4-WIRE INSTALLATION
WARNING
 The neutral wire of 
the supply circuit must be connected to the 
neutral terminal located in the lower center of 
the terminal block. The power leads must be 
connected to the lower left and the lower right 
terminals of the terminal block. The grounding 
lead must be connected to the frame of the 
range with the ground plate and the green 
ground screw.
 FOR POWER CORD INSTALLATION
A. Remove the 3 lower terminal screws 
from the terminal block. Remove the 
ground screw and ground plate and retain 
them. Cut and discard the ground strap. 
DO NOT DISCARD ANY SCREWS.
B. Insert the one ground screw into the power cord 
ground wire terminal ring, through the ground 
plate and into the frame of the range.
C. Insert the 3 terminal screws (removed earlier) 
through each power cord terminal ring and into 
the lower terminals of the terminal block. Be 
certain that the center wire (white/neutral) is 
connected to the center lower position of the 
terminal block. Tighten screws securely into the 
terminal block.
 FOR CONDUIT INSTALLATION
A.  Loosen the 3 lower terminal screws on the 
terminal block. Strip wire to exposed tip about 
5/8” long.
B.  Insert the center (white/neutral) wire tip through 
the bottom center terminal block opening. On 
certain models, the wire will need to be ins 
erted through the ground strap opening and 
then into the bottom center block opening. 
Insert the two side bare wire tips into the lower 
left and the lower right terminal block openings. 
C. Tighten the screws until the wire is firmly 
secured (35 to 50 inch-lbs.). Do not over-tighten 
the screws.
NOTE: ALUMINUM WIRING: Aluminum building wire may be used but it must be rated for the 
correct amperage and voltage. 
Before–Power Cord and Conduit
Terminal 
block
Neutral 
terminal
Ground 
strap
Ground strap 
or
After–Conduit
Terminal 
block
Ground 
plate 
(grounding 
to range)
Wire 
tips
Ground screw
Terminal 
block
Neutral 
terminal
Ground plate 
(grounding to 
range)
Ground 
screw
After–Power Cord
5
 3-WIRE INSTALLATION
WARNING
 The neutral or ground wire of the power cord must be connected to the 
neutral terminal located in the center of the terminal block and the ground strap must connect the 
neutral terminal to the ground plate. The power leads must be connected to the lower left and the 
lower right terminals of the terminal block.
DO NOT remove the ground strap connection.
 FOR POWER CORD INSTALLATION
A. Remove the 3 lower terminal screws from the terminal block. 
B. Insert the 3 terminal screws through each power cord terminal ring and into the lower terminals 
of the terminal block. Be certain that the center wire (white/neutral) is connected to the center 
lower position of the terminal block. 
C. Tighten screws securely into the terminal block.
 FOR CONDUIT INSTALLATION
A.  Loosen the 3 lower terminal screws on the terminal block. Strip wire to expose tip about 5/8” 
long.
B.  Insert the center (white/neutral) wire tip through the bottom center terminal block opening. On 
certain models, the wire will need to be inserted through the ground strap opening and then 
into the bottom center block opening. Insert the two side bare wire tips into the lower left and 
the lower right terminal block openings. 
C. Tighten the screws until the wire is firmly secured (35 to 50 inch-lbs.). Do not over-tighten the 
screws.
NOTE: ALUMINUM WIRING: Aluminum building wire may be used but it must be rated for the 
correct amperage and voltage. 
PROCEED TO STEP 7.
Wire tips
Terminal 
block
Conduit
Ground strap
Terminal block  
(appearance 
may vary)
Neutral terminal
Power cord
Ground 
plate
Power Cord
Conduit