Owner's manual

Fact Sheet Page 2
Materials of Construction
High-pressure piping 316 Stainless Steel, Sch. 10
Low-pressure piping PVC, Sch. 80
Frame Painted blue carbon steel
Enclosure Nema 12
Clamps/fittings Zinc-plated
Membrane Elements and Housings
Membrane Model AG8040F
Style Spiral-wound elements
Manufacturer GE
Membrane type TFC (Polyamide)
Membrane Elements and Housings
continued
Average membrane flux 16-17 gfd
1
Membrane rejection 99.0-99.5 %
Manufacturer GE
Housing material 316 Stainless Steel or FRP
Housing Pressure Rating 31 Bar
1
Flux can be reduced by using 400-sqft membranes.
Cartridge Filtration
Housing model GE HX-0740-80-V316
Housing material 316 Stainless Steel
Cartridge filter 1-micron nominal, ROsave.Z*s
GE PRO Models
MODEL
PRO-11-LA
PRO-23-LA
PRO-34-LA
PRO-45-LA
PRO-102-LA
Permeate Rate
2
:
Concentrate Rate:
Concentrate Recycle:
Feed Rate:
11 m
3
/hr
4 m
3
/hr
2.3 m3/hr
15 m
3
/hr
23 m
3
/hr
7.5 m
3
/hr
2.3 m3/hr
30.5 m
3
/hr
34 m
3
/hr
11 m
3
/hr
NA
45 m
3
/hr
45 m
3
/hr
15 m
3
/hr
3.4 m3/hr
60 m
3
/hr
100 m
3
/hr
34 m
3
/hr
NA
134 m
3
/hr
Pumps and Motors
Model:
Manufacturer:
Quantity:
Motor Power and type:
Installed Power:
Design Flow Rate:
Design boost pressure:
SS8520
Osmonics/Tonkaflo
1
14.9kW (20HP) TEFC
14.9 kW
17 m
3
/hr (75 gpm)
15.9 Bar (230 psig)
SS24011
Osmonics/Tonkaflo
1
37.3 kW (50 Hp) TEFC
37.3 kW
34 m
3
/hr (150 gpm)
15.9 Bar (230 psig)
SS24013
GE/Tonkaflo
1
37.3 KW (50 Hp) TEFC
37.3 KW
45.4 m
3
/hr (200 gpm)
15.9 Bar (230 psig)
AS40410
GE/Tonkaflo
1
37.3 KW (50 Hp) TEFC
37.3 KW
68.1 m
3
/hr (300 gpm)
13.8 Bar (200 psig)
AS40410
GE/Tonkaflo
2
37.3 KW (50 Hp) TEFC
37.3 KW
136 m
3
/hr (600 gpm)
13.8 Bar (200 psig)
Membrane Elements and Housings
Membranes Quantity:
Memb. Housing Style:
Banking Arrangement:
12
4 element long,
4 port
111
24
4 element long,
4 port
321
36
6 element long,
4 port
321
48
4 element long,
4 port
642
108
6 element long,
4 port
963
Cartridge Filtration
Housing Model:
Housing Quantity:
Cartridge Filter Model:
Cartridge Filter Length:
Cartridge Filter Qty:
HX-0740-3.0-V-316
1
RO.Zs01-40XK
102 cm (40”)
7 per housing,
7/change out
HX-0740-3.0-V-316
1
RO.Zs01-40XK
102 cm (40”)
7 per housing,
7/change out
HX-0740-3.0-V-316
2
RO.Zs01-40XK
102 cm (40”)
7 per housing,
14/change out
HX-0740-3.0-V-316
2
RO.Zs01-40XK
102 cm (40”)
7 per housing,
14/change out
HX-0740-3.0-V-316
4
RO.Zs01-40XK
102 cm (40”)
7 per housing,
28/change out
Installation and Utility Requirements
Inlet:
Permeate:
Concentrate:
Inlet Water Pressure:
Air Pressure:
Drain to be Sized for:
Power:
Control Circuit
2.0” flange
1.5” flange
1.0” flange
2 bar, minimum
7 bar, oil-free
15 m
3
/hr (67 gpm)
380-400 VAC, 3-phase,
50Hz
220 VAC, 1-phase, 50Hz
3.0” flange
3.0” flange
1.5” flange
2 bar, minimum
7 bar, oil-free
30 m
3
/hr (133 gpm)
380-400 VAC, 3-phase,
50Hz
220 VAC, 1-phase, 50Hz
3.0” flange
3.0” flange
1.5” flange
2 bar, minimum
7 bar, oil-free
45.4 m
3
/hr (200 gpm)
380-400 VAC, 3-phase,
50Hz
220 VAC, 1-phase, 50Hz
4.0” flange
3.0” flange
2.0” flange
2 bar, minimum
7 bar, oil-free
60.6 m
3
/hr (267 gpm)
380-400 VAC, 3-phase,
50Hz
220 VAC, 1-phase, 50Hz
6.0” flange
6.0” flange
3.0” flange
2 bar, minimum
7 bar, oil-free
136 m
3
/hr (600 gpm)
380-400 VAC, 3-phase,
50Hz
220 VAC, 1-phase, 50Hz
Skid
Height:
Width:
Depth:
Shipping Weight
Estimate:
193 cm (76)
117 cm (46)
493 cm (194)
1542 kg (3400 lb)
193 cm (76)
117 cm (46)
493 cm (194)
2040 kg (4500 lb)
193 cm (76)
117 cm (46)
696 cm (274)
2720 kg (6000 lb )
193 cm (76)
203 cm (80)
493 cm (194)
3175 kg (7000 lb)
193 cm (76)
203 cm (80)
696 cm (274)
6350 kg (14,000 lb)
2
Maximum permeate rate listed at design temperature. Permeate rate can be reduced by up to 15%.