GE MultiLink Submittal
Rev. Aug. 2022
MULTILINK SERIES SUBMITTAL
36000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM
ASH436JCDDA
Capacity and power usage are measured under the assumption of indoor humidity of 46%
Capacity and power usage are measured under the assumption of indoor humidity of 46%
Heating Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
-4
O
F (-20
O
C) 18,900 3,125 1.77 18,000 3,100 1.70 17,100 3,075 1.63
5
O
F (-15
O
C) 23,100 3,705 1.83 22,000 3,680 1.75 20,900 3,655 1.68
17
O
F (-8
O
C) 31,500 4,725 1.95 30,000 4,700 1.87 28,500 4,675 1.79
47
O
F (8
O
C) 45,360 4,825 2.76 43,200 4,800 2.64 41,040 4,775 2.52
Heating Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
-4
O
F (-20
O
C) 17,850 3,305 1.58 17,000 3,280 1.52 16,150 3,255 1.45
5
O
F (-15
O
C) 22,050 3,445 1.88 21,000 3,420 1.80 19,950 3,395 1.72
17
O
F (-8
O
C) 33,600 5,205 1.89 32,000 5,180 1.81 30,400 5,155 1.73
47
O
F (8
O
C) 45,360 5,305 2.51 43,200 5,280 2.40 41,040 5,255 2.29
Cooling Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
14
O
F (-10
O
C) 39,163 4,723 2.43 40,193 4,771 2.47 41,224 4,820 2.51
23
O
F (-5
O
C) 39,962 4,779 2.45 41,013 4,827 2.49 42,065 4,876 2.53
32
O
F (0
O
C) 40,777 4,835 2.47 41,850 4,883 2.51 42,923 4,933 2.55
50
O
F (10
O
C) 41,609 4,890 2.49 42,704 4,939 2.53 43,799 4,990 2.57
65
O
F (18
O
C) 43,799 5,057 2.54 44,951 5,108 2.58 46,104 5,160 2.62
75
O
F (24
O
C) 43,411 5,224 2.44 44,554 5,276 2.47 45,696 5,330 2.51
85
O
F (29
O
C) 42,636 5,390 2.32 43,758 5,445 2.36 44,880 5,500 2.39
95
O
F (35
O
C) 38,760 5,557 2.04 39,780 5,613 2.08 40,800 5,670 2.11
105
O
F (41
O
C) 29,070 6,113 1.39 29,835 6,174 1.42 30,600 5,954 1.51
115
O
F (46
O
C) 20,969 5,835 1.05 21,521 5,894 1.07 22,073 6,010 1.08
Cooling Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
14
O
F (-10
O
C) 39,163 4,831 2.38 40,193 4,881 2.41 41,224 4,930 2.45
23
O
F (-5
O
C) 39,962 4,888 2.40 41,013 4,938 2.43 42,065 4,988 2.47
32
O
F (0
O
C) 40,777 4,945 2.42 41,850 4,996 2.46 42,923 5,046 2.49
50
O
F (10
O
C) 41,609 5,002 2.44 42,704 5,053 2.48 43,799 5,104 2.52
65
O
F (18
O
C) 43,799 5,172 2.48 44,951 5,225 2.52 46,104 5,278 2.56
75
O
F (24
O
C) 43,411 5,343 2.38 44,554 5,397 2.42 45,696 5,452 2.46
85
O
F (29
O
C) 42,636 5,513 2.27 43,758 5,570 2.30 44,880 5,626 2.34
95
O
F (35
O
C) 38,760 5,684 2.00 39,780 5,742 2.03 40,800 5,800 2.06
105
O
F (41
O
C) 29,070 6,252 1.36 29,835 6,316 1.38 30,600 6,380 1.41
115
O
F (46
O
C) 21,851 5,968 1.07 22,426 6,029 1.09 23,001 6,090 1.11