GE Wall Mount Installation Manual
Table Of Contents
31-5000560 Rev. 3 11
Step 2 - Installation of the Indoor Unit (Cont.)
Installation Instructions
D. Electrical Connections for the Indoor Unit
NOTE: Be certain all wiring complies with local building 
codes and NEC and that the supply voltage for this system is 
correct.
• Place the indoor unit on a solid work surface before making 
electrical connections.
• To make the electrical connections for the indoor unit, both 
the outer plastic and inner galvanized steel cover plate must 
be removed.
• Raise the front cover to access the screws for removing 
these covers. 
• Route the 14/4 AWG stranded wiring through the slot in the 
back of the unit and into the front access panel.
• Using a wire stripper, remove the insulation and separate 
the 4 wires.
• Make wiring connections at each terminal according to 
wiring diagram. (Take note of the color of the wire at each 
terminal and ensure the wires are connected to the outdoor 
unit accordingly.)
• Ensure each wire is under the screw terminal plate and the 
plate is tightened.
• Ensure the 14/4 cable is secured under the strain relief 
bracket. 
• Replace both cover plates and lower the front casing after 
the terminal block wiring is completed.
E. Mount Indoor Unit to Mounting Plate
• Bundle the refrigerant piping, drain piping, and wiring 
with tape and carefully route the bundle through the 
piping hole.
• With the top of the indoor unit closer to the wall, hang 
the indoor unit on the upper hooks of the mounting 
plate. Slide the unit slightly side to side to verify 
proper placement.
• Rotate the lower portion of the indoor unit to the 
mounting plate, pushing the unit up slightly, rotate the 
lower part of the unit fully against the wall, then pull 
down do the lower hooks engage the brackets. (see 
illustration)
• Verify the unit is secured and flush to the wall.
• Indoor Unit installation is finished at this time.
F. Condensate Drainage Pipe
• Verify the condensate drain line has a constant pitch 
downward for proper water flow. There should be no 
kinks or rises in the tubing which may cause a trapping 
effect of the water (see illustration).
 Optional: Can use PVC pipe by connecting a 1” ID PVC 
pipe to the drain line coming out of the wall and running to 
desired location.
mounting plate
G. To Remove the Indoor Unit
• Slightly raise the entire unit.
• Pull the lower portion of the unit off the lower hooks and pull 
slightly away from the wall.
• Lift the upper portion of the unit off the upper hooks.
C. Install the Tubing 
• Always use new clean copper tubing. Never reuse tubing if 
replacing an existing system. 
• Measure and mark the location where the piping hole is to 
be drilled.
• Follow these steps to move the drain pipe if pipe location 
will be on the left side of the unit.
1. Remove the stopper in the left drain hole and knockout the 
molded plug inside the port.
2. Transfer the corrugate drain hose from the right side to the 
left side.
3. Insert stopper into right side drain port. Using soap as 
a lubricant and a small screwdriver will allow for easier 
seating of the stopper.
• Drill the lineset hole using a 2 1/4” hole saw. Angle the drill 
with a downward pitch to the outside wall so that the outside 
wall hole will be at least a ¼” lower than the inside hole. 
This allows for proper drainage of condensate.
• Install the lineset hole flange at the hole opening on the 
inside wall.
NOTE: The flange is prescored. It may be necessary to 
modify the flange to fit properly behind the wall unit housing.
It becomes
high midway.
The gap with the
ground is too small
There is the bad
smell from a sewer
It waves.
The end is imm-
ersed in water.
Less than
5cm










