GE MultiLink Submittal

Rev. Aug. 2022
MULTILINK SERIES SUBMITTAL
24000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM
ASH324JCDDA
Capacity and power usage are measured under the assumption of indoor humidity of 46%
Capacity and power usage are measured under the assumption of indoor humidity of 46%
Heating Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
-4
O
F (-20
O
C) 12,600 2,095 1.76 12,000 2,070 1.70 11,400 2,045 1.63
5
O
F (-15
O
C) 14,595 2,065 2.07 13,900 2,040 2.00 13,205 2,015 1.92
17
O
F (-8
O
C) 21,000 2,595 2.37 20,000 2,570 2.28 19,000 2,545 2.19
47
O
F (8
O
C) 31,500 2,845 3.25 30,000 2,820 3.12 28,500 2,795 2.99
Heating Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
-4
O
F (-20
O
C) 11,550 2,115 1.60 11,000 2,090 1.54 10,450 2,065 1.48
5
O
F (-15
O
C) 12,600 1,805 2.05 12,000 1,780 1.98 11,400 1,755 1.90
17
O
F (-8
O
C) 21,000 2,775 2.22 20,000 2,750 2.13 19,000 2,725 2.04
47
O
F (8
O
C) 31,500 3,075 3.00 30,000 3,050 2.88 28,500 3,025 2.76
Cooling Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
14
O
F (-10
O
C) 25,800 2,241 3.37 26,479 2,264 3.43 27,158 2,287 3.48
23
O
F (-5
O
C) 26,326 2,267 3.40 27,019 2,290 3.46 27,712 2,313 3.51
32
O
F (0
O
C) 26,864 2,293 3.43 27,571 2,317 3.49 28,278 2,340 3.54
50
O
F (10
O
C) 27,412 2,320 3.46 28,134 2,343 3.52 28,855 2,367 3.57
65
O
F (18
O
C) 28,855 2,399 3.53 29,615 2,423 3.58 30,374 2,448 3.64
75
O
F (24
O
C) 28,601 2,478 3.38 29,353 2,503 3.44 30,106 2,529 3.49
85
O
F (29
O
C) 28,090 2,557 3.22 28,829 2,583 3.27 29,568 2,609 3.32
95
O
F (35
O
C) 25,536 2,636 2.84 26,208 2,663 2.88 26,880 2,690 2.93
105
O
F (41
O
C) 22,982 2,900 2.32 23,587 2,929 2.36 24,192 2,959 2.40
115
O
F (46
O
C) 19,152 2,768 2.03 19,656 2,796 2.06 20,160 2,825 2.09
Cooling Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
14
O
F (-10
O
C) 25,340 2,499 2.97 26,007 2,525 3.02 26,674 2,550 3.07
23
O
F (-5
O
C) 25,857 2,528 3.00 26,538 2,554 3.05 27,218 2,580 3.09
32
O
F (0
O
C) 26,384 2,558 3.02 27,079 2,584 3.07 27,773 2,610 3.12
50
O
F (10
O
C) 26,923 2,587 3.05 27,632 2,614 3.10 28,340 2,640 3.15
65
O
F (18
O
C) 28,340 2,675 3.11 29,086 2,703 3.15 29,832 2,730 3.20
75
O
F (24
O
C) 28,090 2,764 2.98 28,829 2,792 3.03 29,568 2,820 3.07
85
O
F (29
O
C) 27,588 2,852 2.84 28,314 2,881 2.88 29,040 2,910 2.92
95
O
F (35
O
C) 25,080 2,940 2.50 25,740 2,970 2.54 26,400 3,000 2.58
105
O
F (41
O
C) 22,572 3,234 2.05 23,166 3,267 2.08 23,760 3,300 2.11
115
O
F (46
O
C) 18,810 3,087 1.79 19,305 3,119 1.81 19,800 3,150 1.84