GE MultiLink Submittal
Rev. Aug. 2022
MULTILINK SERIES SUBMITTAL
18000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM
ASH218JCDDA
Capacity and power usage are measured under the assumption of indoor humidity of 46%
Capacity and power usage are measured under the assumption of indoor humidity of 46%
Heating Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
-4
O
F (-20
O
C) 11,970 1,935 1.81 11,400 1,910 1.75 10,830 1,885 1.68
5
O
F (-15
O
C) 14,385 2,255 1.87 13,700 2,230 1.80 13,015 2,205 1.73
17
O
F (-8
O
C) 15,960 1,725 2.71 15,200 1,700 2.62 14,440 1,675 2.53
47
O
F (8
O
C) 25,200 2,535 2.91 24,000 2,510 2.80 22,800 2,485 2.69
Heating Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
Max Heating
Capacity (Btu/h)
Power Usage
(w) COP
-4
O
F (-20
O
C) 9,660 1,775 1.60 9,200 1,750 1.54 8,740 1,725 1.48
5
O
F (-15
O
C) 11,550 2,035 1.66 11,000 2,010 1.60 10,450 1,985 1.54
17
O
F (-8
O
C) 15,960 2,085 2.24 15,200 2,060 2.16 14,440 2,035 2.08
47
O
F (8
O
C) 23,940 2,285 3.07 22,800 2,260 2.96 21,660 2,235 2.84
Cooling Capacity Data - Non Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
14
O
F (-10
O
C) 20,734 1,799 3.38 21,279 1,817 3.43 21,825 1,836 3.48
23
O
F (-5
O
C) 21,157 1,821 3.41 21,713 1,839 3.46 22,270 1,858 3.51
32
O
F (0
O
C) 21,588 1,842 3.43 22,156 1,860 3.49 22,724 1,879 3.54
50
O
F (10
O
C) 22,029 1,863 3.47 22,608 1,881 3.52 23,188 1,901 3.57
65
O
F (18
O
C) 23,188 1,926 3.53 23,798 1,946 3.58 24,408 1,966 3.64
75
O
F (24
O
C) 22,982 1,990 3.38 23,587 2,010 3.44 24,192 2,030 3.49
85
O
F (29
O
C) 22,572 2,053 3.22 23,166 2,074 3.27 23,760 2,095 3.32
95
O
F (35
O
C) 20,520 2,117 2.84 21,060 2,138 2.89 21,600 2,160 2.93
105
O
F (41
O
C) 18,468 2,329 2.32 18,954 2,352 2.36 19,440 2,376 2.40
115
O
F (46
O
C) 15,390 2,223 2.03 15,795 2,245 2.06 16,200 2,268 2.09
Cooling Capacity Data - Ducted
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
Maximum Cooling
Capacity (Btu/h)
Power Usage
(w)
EER
14
O
F (-10
O
C) 20,734 1,949 3.12 21,279 1,969 3.17 21,825 1,989 3.22
23
O
F (-5
O
C) 21,157 1,972 3.14 21,713 1,993 3.19 22,270 2,012 3.24
32
O
F (0
O
C) 21,588 1,995 3.17 22,156 2,016 3.22 22,724 2,036 3.27
50
O
F (10
O
C) 22,029 2,018 3.20 22,608 2,039 3.25 23,188 2,059 3.30
65
O
F (18
O
C) 23,188 2,087 3.26 23,798 2,108 3.31 24,408 2,129 3.36
75
O
F (24
O
C) 22,982 2,155 3.13 23,587 2,178 3.17 24,192 2,200 3.22
85
O
F (29
O
C) 22,572 2,224 2.97 23,166 2,247 3.02 23,760 2,270 3.07
95
O
F (35
O
C) 20,520 2,293 2.62 21,060 2,317 2.66 21,600 2,340 2.70
105
O
F (41
O
C) 18,468 2,522 2.15 18,954 2,549 2.18 19,440 2,574 2.21
115
O
F (46
O
C) 15,390 2,408 1.87 15,795 2,433 1.90 16,200 2,457 1.93