GE MultiLink Submittal
Rev. Aug. 2022
MULTILINK SERIES SUBMITTAL
12000 BTU/HR MID-STATIC DUCTED INDOOR
USYM12UCDSA
Performance
Rated Cooling Capacity 12,000 BTU
Rated Heating Capacity 13,000 BTU
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Indoor Unit
Uncrated Dimension (HxWxD)
9 3/4 x 27 1/2 x 27 1/2 in
(248 x 700 x 700 mm)
Crated (HxWxD)
13 1/4 x 37 1/2 x 35 1/2 in
(340 x 950 x 900 mm)
Maximum ESP (IWC) 0.6
Airflow CFM
(Turbo/High/Med/Low)
494/423/352/264
Indoor Sound Level dB
(Turbo/High/Med/Low)
35/32/29/26
Motor Rating (HP) 0.18
Heat Exchanger Fin Type Blue Fin
Condensate Pump Included - 39 in. Lift
Weight (Ship/Net) 57/66 lbs
Piping
Flare Connections
1/4” (Liquid)
3/8” (Vapor)
Drain Pipe 1 1/4”
For more information visit us:
www.geappliances.com/ductless
Job Name: _______________________________
Purchaser: _______________________________
Submitted To: ____________________________
Construction: ____________________________
Reference: _______________________________
Approval: ________________________________
Date: ___________________________________
Submitted By: ___________________________
Unit: ___________________________________
Drawing #: _______________________________
Accessories
Wired Controller
Controller must be ordered separately
Compatible With
Simplified Wired Controller (ACT17CWA)
Built-in WiFi
Supply Plenum
UAPT0912A
Return MERV Filter Box
UAMFB0912A