Installation Instructions
Step 3 - Installation of the Outdoor Unit (Cont.)
Line Set Connections
Model  ASH436JCDDA1 ASH324JCDDA1 ASH218JCDDA1 ASH220NCDWA ASH324NCDWA
Connection priority is 
largest indoor unit on lowest 
terminal set (D), and install 
remaining indoor units from 
bottom to top.
When there are two indoors, 
the prior service valves are 
D C C B B A B A C B
When there are three indoors, 
the prior service valves are
D C B C B A / / C B A
When there are four indoors, 
the prior service valves are
D C B A / / / /
NOTE: Please execute as the above when connecting indoor unit for better oil return and more reliable system. 
NOTE: No connection priority on ASH436NCDWA1
LED A B C D E Message
LED status 
example for 
ASH324JCDDA1 
model
OFF No power to unit
ALL Flashing Outdoor unit searching for indoor units at initial start-up. If flashing 
continues, check wiring for proper type and connections
ALL ON All units connected correctly
ON Flashing Flashing ON Flashing ON: unit connected correctly
Flashing: IDU not communicating. Check wiring and connections 
among B, C & E
Only one LED flashing
Model Number Factory 
Charge
Total Pipe 
Length of factory 
charge
Additional 
charge rule
Branch 
Maximum 
pipe length
System 
Maximum 
pipe length
Minimum pipe length
Unit oz ft oz/ft ft ft ft
ASH218JCDDA1 60 50 0.2 65 98 6’ per indoor and 20’ per system
ASH324JCDDA1 67 100 0.2 82 197 6’ per indoor and 20’ per system
ASH436JCDDA1 90 131 0.2 82 230 6’ per indoor and 20’ per system
ASH220NCDWA 99 100 0.2 82 164 6’ per indoor and 20’ per system
ASH324NCDWA 99 100 0.2 82 197 6’ per indoor and 20’ per system
ASH436NCDWA1 113 131 0.2 82 230 6’ per indoor and 25’ per system
Refrigerant Charge and Pipe Length Information
D. Wiring Check Test
Turn off power at the disconnect. Move all dip switches 
in the SW1 bank to ON. When power is turned on, the 
LED display will alternate the compressor frequency and 
CH (check). The system will run through each unit (A, 
B, and C), cycling each EEV while testing the wiring. A 
successful test will be indicated by the corresponding 
LED displaying a constant green (1=A, 2=B, 3=C). Mis-
wired units will generate an EC on the display, with the 
corresponding LED flashing green.
Note: This LED display layout only 
applies to ASH436JCDDA1