GE Altitude Series Submittal

ALTITUDE SERIES SUBMITTAL
Rev. May 2020
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 30A
MCA 20A
Heating Performance
Rated Heating Capacity 27,600 BTU
Heating Capacity Range 6,200~36,000 BTU
Rated Power Input 2,630 W
HSPF 10.0
Operating Range
Cooling 14~115°F (-10~46°C)
Heating -15~75°F (-26~24°C)
CUS
Intertek
24000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM
ASH124PRDWA / ASYW24PRDWB
Pipe Length
Minimum Pipe Length 6 ft
Maximum Pipe Length 83 ft
Maximum Pipe Height Dierence 50 ft
Connection
1/4”(Discharge)
1/2”(Suction) Flare
Cooling Performance
Rated Cooling Capacity 22,000 BTU
Cooling Capacity Range 6,400~30,000 BTU
Rated Power Input 1,760 W
SEER 20.0
EER 12.5
Moisture Removal 7.0 Pt./Hr
ACCESSORIES
Remote Controller
Ships with indoor unit
Wired Controller
ASYW24PRDWB units are compatible with wired
controller ACT17CWA with the interface kit WK-B
WiFi
ASYW24PRDWB units are compatible with WiFi USB
adapter AWF01RWA
Job Name: _______________________________
Purchaser: _______________________________
Submitted To: ____________________________
Construction: ____________________________
Reference: _______________________________
Approval: ________________________________
Date: ___________________________________
Submitted By: ___________________________
Unit: ___________________________________
Drawing #: _______________________________
For more information visit us:
www.geappliances.com/ductless