User's Manual Part 2
88 Mercury Reference Manual 05-4446A01, Rev. D
3.6.2 Menu Selections
Connect a PC to the transceiver as described in STEP 3—CONNECT PC
TO THE TRANSCEIVER
section on Page 25, and access the embedded
management system. Follow the steps below to proceed with
Modbus/TCP configuration.
1. From the Serial Configuration Wizard opening screen (Figure 3-52
on Page 88
), select
A to begin the wizard.
Invisible place holder
Figure 3-52. Configuration Wizard Opening Screen
2. Choose the IP protocol you wish to use (TCP, UDP, or Mod-
bus/TCP) by selecting the appropriate letter from the menu.
Figure 3-53. IP Protocol Selection Screen
3. On the next screen (
Figure 3-54 on Page 89), choose the listening
port you wish to use for the Modbus/TCP server. The default is port
502. Press N to continue.