User Guide
Simon Security System
49
Figure 13. Diagram of Smoke Detector Locations
Appendix A: Troubleshooting
System Status
How to clear SYSTEM STATUS (Alarm Memory)
From a disarmed state press SYSTEM STATUS, listen to the status message, then press
DISARM.
Panel announces Siren 1 failure or Siren 2 failure.
• Turn option 53 off if a hardwire siren or sensor is not connected.
• Check for the correct end-of-line resistor in HWIN 1 and 2 circuits.
Panel announces Low Battery.
• Check that panel backup battery is connected.
Panel announces Option 50 Detected.
• Option 50 is RF jam detect. The control panel has detected RF interference.
Living
Room
Dining
Room
Basement
x
H
Hall
Bedroom
Bedroom
Living
Room
Recreation
Room
Basement
Hall
Bedroom
Bedroom
Living
Room
Dining
Room
Hall
Bedroom
Bedroom
Bedroom
Kitchen
A smoke detector should
be located on each level.
Smoke detectors should
be located between the
sleeping area and the rest
of the family living unit.
NOTE: Do not install smoke detectors where normal ambient temperatures are above
100°F or below 40°F. Also, do not locate detectors in front of AC/ Heat
registers or other locations where normal air circulation will keep smoke
from entering the detector.
NOTE: Additional information on household fire warning is available at nominal
cost from: The National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269. Request Standard No. NFPA74.
H
x
Living
Room
Bedroom
Bedroom
Bedroom
Dining
Room
Kitchen
TV
Room
In family living units with more
than one sleeping area, locate a
smoke detector at each area.
H
NOTE: Ceiling-mounted smoke detectors should be located in the center of the room
or hall, or not less than 4 inches from the wall. When the detector is mounted
on the wall, the top of the detector should be 4 to 12 inches from the ceiling.
Required smoke detector
Heat detector
Indicates smoke detector is optional if door is not provided between
basement and recreation rooms.
8557144a