663 / 664E Installation Guide
CC848921016 r02 December 2012 Page 8
Step 4 Run and Terminate Alarm Cabling
Run and terminate alarm cabling
Jumper settings are available for both
Close on Alarm and Open on Alarm
extensions
Verify alarm extensions with the Alarm
Center
See Pulsar Edge Controller Family
Product Manual for additional information
Step 5 Run & Term. Supply and Return Cables
Output cabling
With GMT fuses and circuit breakers
removed, land all supply and return cabling
at the rear of the system
Circuit breaker lug landings -
1/4” on 5/8 inch centers
Torque to 240 in-lb
GMT wire landings
Strip wire 3/8
Torque to 13 in-lb
Connectorized
Alarm Cable
connection
Front
Circuit breaker
landing positions
GMT
landing positions