12V Austin MicroLynx
TM
5A: Non-Isolated DC-DC Power Modules
10Vdc –14Vdc input; 0.75Vdc to 5.5Vdc output; 5A Output Current
May 6, 2013 ©2013 General Electric Company. All rights reserved. Page 2
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings
only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations
sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter Device Symbol Min Max Unit
Input Voltage All V
IN
-0.3 15 Vdc
Continuous
Operating Ambient Temperature All T
A
-40 85 °C
(see Thermal Considerations section)
Storage Temperature All T
stg
-55 125 °C
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions.
Parameter Device Symbol Min Typ Max Unit
Operating Input Voltage All V
IN
10 12 14 Vdc
Maximum Input Current All I
IN,max
3.5 Adc
(V
IN
= V
IN, min
to V
IN, max
, I
O
=I
O, max
)
Input No Load Current V
O,set
= 0.75 Vdc I
IN,No load
17 mA
(V
IN
= V
IN, nom
, Io = 0, module enabled) V
O,set
= 5.0Vdc I
IN,No load
100 mA
Input Stand-by Current All I
IN,stand-by
1.2 mA
(V
IN
= V
IN, nom
, module disabled)
Inrush Transient All I
2
t 0.4 A
2
s
Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 1μH source impedance; V
IN, min
to V
IN,
max,
I
O
= I
Omax
; See Test configuration section)
All 30 mAp-p
Input Ripple Rejection (120Hz) All 30 dB
CAUTION: This power module is not internally fused. An input line fuse must always be used.
This power module can be used in a wide variety of applications, ranging from simple standalone operation to being part of a
complex power architecture. To preserve maximum flexibility, internal fusing is not included, however, to achieve maximum safety
and system protection, always use an input line fuse. The safety agencies require a fast-acting fuse with a maximum rating of 6 A
(see Safety Considerations section). Based on the information provided in this data sheet on inrush energy and maximum dc input
current, the same type of fuse with a lower rating can be used. Refer to the fuse manufacturer’s data sheet for further information.