Installation Guide
Re-apply
power
to fi xture
and ensure
proper oper-
ation.
Install
Type B
double ended
tubes.
9
8
Installation Guide LEDL136 | DOC-2001746
LED Double Ended Type B
T8 Tubes (120V to 347V)
LED15BDT8/G4/RXX/@
The Type B LED T8 Tubes listed above are to be used with G13 (medium
bi-pin) lamp holders that are either internally or externally shunted.
BEFORE YOU BEGIN
Read these instructions completely and carefully.
R is a number representing CRI; XX are numbers representing CCT,
@ may be any character(s) representing additional lamp features
WARNING
RISK OF FIRE OR ELECTRIC SHOCK: LED Retrofi t Kit installation requires knowledge of luminaire electrical systems. If not
qualifi ed, do not attempt installation. Contact a qualifi ed electrician. Install this kit only in luminaries that have the construction
features and dimensions shown in the drawings and where the input rating of the retrofi t kit does not exceed the input rating
of the luminaire. To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
Installers should not disconnect existing wires from lampholder terminals to make new connections at lampholder terminals.
Instead installers should cut existing lampholder leads away from the lampholder and make new electrical connections to the
lampholder lead wires by employing applicable connectors (or replace with new shunted lamp holders). THIS RETROFIT KIT
IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION SHALL BE DETERMINED
BY AUTHORITIES HAVING JURISDICTION. PRODUCT MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE
WITH THE APPLICABLE AND APPROPRIATE ELECTRICAL CODES. THE INSTALLATION GUIDE DOES NOT SUPERCEDE LOCAL OR
NATIONAL REGULATIONS FOR ELECTRICAL INSTALLATIONS. Installers should examine all parts that are not intended to be
replaced by the retrofi t kit for damage and replace any damaged parts prior to installation of the retrofi t kit. Do not make or
alter any open holes in an enclosure of wiring or electrical components during kit installation. This lamp operates directly from
120V-347V mains. Do not use Ballast or any starting aid. Do not connect to a voltage higher than 347 volts. To reduce risk of
misapplication, Current recommends installing a fuse in series with the Phase or Hot lead and the SHUNTED (Instant Start style)
lamp holder(s) per the wiring diagrams below. Only one fuse kit is needed for up to 4 tubes in the same fi xture. Ensure the lamp
holders are SHUNTED for Double Ended T8 applications.
2
Ensure
power
is off to
luminaire by
disconnect-
ing the sup-
ply voltage.
Install the
retrofi t kit
Caution label in an
easy to see location
to ensure the user
understands the
system now uses
LED Type B double
ended tubes, and
the use of fl uores-
cent lamps may
result in damage or
injury.
Installation Instructions
Remove all
fl uorescent
lamps and bal-
last/wiring area
cover. Cut the
ballast lead wires
about 6 inches
away from each
lamp holder.
1 82 9
www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the General Electric Company and are used under
license. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.
LEDL136 (Rev 8/9/21) - DOC-2001746
To install the Type B LED T8, please read the entire installation guide carefully.
To protect against future misapplication, Current recommends installing
an in-line fuse: Type 2AG, rated at 1 amp, 500 volts, Littlefuse part number
0477001.MXP or equivalent.
Ensure that package includes installation guide, warning label to be attached to luminaire, LED T8 tube. Minimum fi xture volume for 4 lamps is 48 inches long x 24
inches wide x 4 inches deep (4’). Minimum socket spacing is 4.4 inches apart. Product is not intended to be used with dimmers or emergency lighting. This LED T8
tube is not suitable for direct replacement of linear fl uorescent lamps in luminaires where the lamps are connected to a ballast. The technical and safety require-
ments of the converted luminaire are the sole responsibility of the party doing the conversion and shall comply with the local applicable safety and regulatory laws
and standards. The provided Caution label should be placed onto the converted luminaire to indicate that the luminaire has been modifi ed and can no longer be
used with conventional fl uorescent lamps.
This lamp is designed for general lighting service. This lamp may not be suitable for use in all applications where a conventional fl uorescent lamp has been used.
This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation. Any changes or modifi cations not expressly approved by the manu-
facturer could void the user’s authority to operate the equipment. This device complies with CAN ICES-005A.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
3) If two wires come from an existing lamp holder
(rapid start type), these two wires should be wired
or shunted together.
4) Connect the recommended fuse and fuseholder (not
supplied) to the black (hot) wire from the mains.
5) Connect together all of the lampholder leads on one
side and connect to the other side of the recommended
fuse with suitable wire.
6) Connect together all of the lamp holder leads on the
other side of the fi xture and connect to the white or neu-
tral wire from the mains.
7) Replace the ballast / wiring area cover, ensuring no
wires are pinched between the cover and the fi xture.
10
3 7
1A
FUSE
1A
FUSE
1A
FUSE
1A
FUSE