Accessory Guide
Specifications subject to change.
Total watts and total amps include electric heat and fan motor(s).
RAK515P, RAK520P and RAK530P are only to be used with a sub-base.
*30 AMP heater wattage will be reduced in low fan operation.
Each line cord kit has an integral Leakage Current Detection and Interruption (LCDI) device as required by
National Electrical Code (NEC) and Underwriters Laboratories (UL) for units manufactured after August 1, 2004.
230/208-Volt Line-Cord Connected (P) and Direct Connected Units (D)
BTUh size 7,000/9,000 12,000/15,000
Power connection kit
RAK315P &
RAK315D
RAK320P &
RAK320D
RAK330P &
RAK330D
RAK315P &
RAK315D
RAK320P &
RAK320D
RAK330P &
RAK330D
Total watts 2,410/1,990 3,420/2,830 4,830/3,990* 2,430/2,020 3,450/2,860 4,860/4,020*
Heater watts 2,400/1,960 3,400/2,780 4,800/3,930* 2,400/1,960 3,400/2,780 4,800/3,930*
Heater BTUh 8,100/6,600 11,600/9,400 16,300/13,400* 8,100/6,600 11,600/9,400 16,300/13,400*
Total amps 10.5/9.6 14.9/13.6 21.0/19.2 10.6/9.7 15.1/13.8 21.2/19.3
MCA 15 20 25 15 20 25
Recommended
protective device
(MOCP)
15 amp
time-delay fuse
or breaker
20 amp
time-delay fuse
or breaker
30 amp
time-delay fuse
or breaker
15 amp
time-delay fuse
or breaker
20 amp
time-delay fuse
or breaker
30 amp
time-delay fuse
or breaker
265-Volt Permanent (P, Cord Set) and Direct-Connected Units (D)
BTUh size 7,000/9,000 12,000/15,000
Power connection kit
RAK515P &
RAK515D
RAK520P &
RAK520D
RAK530P &
RAK530D
RAK515P &
RAK515D
RAK520P &
RAK520D
RAK530P &
RAK530D
Total watts 2,440 3,450 4,850* 2,460 3,470 4,870*
Heater watts 2,400 3,400 4,800* 2,400 3,400 4,800*
Heater BTUh 8,100 11,600 16,300* 8,100 11,600 16,300*
Total amps 9.1 12.9 18.1 9.3 13.1 18.4
MCA 15 20 25 15 20 25
Recommended
protective device
(MOCP)
15 amp
time-delay fuse
or breaker
20 amp
time-delay fuse
or breaker
25 amp
time-delay fuse
or breaker
15 amp
time-delay fuse
or breaker
20 amp
time-delay fuse
or breaker
25 amp
time-delay fuse
or breaker
GE ZONELINE SPECIFICATIONS —RESISTANCE HEATER WATTAGE
POWER CONNECTION KITS
Required on all models. See specification information below for heater kWh and branch circuit ampacity.
GE Zoneline offers short and long power cords, direct connect universal supply kits and sub bases.
Power connection kits are required for all models. See pages 11 and 12 for all product options.
Receptacles/Sub-bases
Tandem
230/208V 15 Amp
NEMA6-15R
Perpendicular
230/208V 20 Amp
NEMA6-20R
Large tandem
230/208V 30 Amp
NEMA6-30R
265V 15 amp
NEMA7-15R;
receptacle used on
265V sub-base
265V 20 amp
NEMA7-20R;
receptacle used on
265V sub-base
265V 30 amp
NEMA7-30R;
receptacle used on
265V sub-base
The correct kit for the installation is determined by the voltage and amperage of the electrical circuit
and the means of connecting the unit to the building wiring. If the unit is to be plugged into a receptacle,
a line cord kit would be used; if the unit is to be permanently connected, a direct connect or permanent
connection kit would be used. Cord set units of 265 volts must be installed in compliance with
National Electrical Code. (Article 440.60)
GE ZONELINE SPECIFICATION — RESISTANCE HEATER WATTAGE
ELECTRICAL CONNECTION/SUB-BASE
VISIT ZONELINE.COM OR CALL 888.231.2548