Accessory Guide
265V Models AZ45E09EAP AZ45E12EAP
Cooling BTUH 9,400 10,900
EER (BTU/Watt) 12.1 11.0
Dehumidification Pts/Hr 3.5 4.2
Refrigerant type R-410A R-410A
CFM, indoor fan high 370 360
CFM, indoor fan low 260 270
Vent CFM (full open)* 44 44
Power factor 93% 97%
Sensible heat ratio
@ 265 volts 58% 54%
Cooling Watts 780 995
Total Cooling Amperes, F.L. 3.2 3.9
Heating Amperes 16.5 23.5
Weight (Net/Ship) 109/119 112/122
*Using RAKVENT1 kit
Specifications subject to change.
NOTE: Resistance heater wattage and amperage dependent on power
connection kit. See page 6.
265V Models AZ65H07EAC AZ65H09EAC AZ65H12EAC AZ65H15EAC
Cooling BTUH 7,000 9,500 11,500 14,200
EER (BTU/Watt) 12.8 11.7 11.2 10.2
Dehumidification Pts/Hr 1.5 2.5 3.7 4.8
Refrigerant type R-410A R-410A R-410A R-410A
CFM, indoor fan high 360 420 410 400
CFM, indoor fan low 205 300 300 290
Vent CFM (full open)* 38 40 45 44
Power factor 95% 94% 97% 97%
Sensible heat ratio
@ 265 volts 77% 68% 62% 60%
Cooling Watts 545 810 1,025 1,390
Total Cooling Amperes, F.L. 2.2 3.3 4.0 5.5
Amperes, L.R. 11.7 16.5 23.5 29.0
Reverse cycle heat BTUH 6,200 8,100 10,000 13,400
Coefficient of Performance 3.9 3.6 3.5 3.3
Heat Pump Watts 460 655 835 1,225
Heat Pump Amperes 1.9 2.8 3.5 4.9
Weight (Net/Ship) 98/108 104/114 104/114 109/119
265V Models AZ65H07EBM AZ65H09EBM AZ65H12EBM
Cooling BTUH 6,900 9,200 11,600
EER (BTU/Watt) 12.5 11.5 11.3
Dehumidification Pts/Hr 0.7 2.0 3.7
Refrigerant type R-410A R-410A R-410A
CFM, indoor fan high 409 409 449
CFM, indoor fan low 350 370 350
Vent CFM 25-50 25-50 25-50
Power factor 93% 93% 96%
Sensible heat ratio
@ 230 volts 88% 78% 69%
Cooling Watts 550 800 1,025
Total Cooling Amperes, F.L. 3.2 4.2 4.0
Amperes, L.R. 11.7 16.5 23.5
Reverse cycle heat BTUH 6,000 8,100 10,000
Coefficient of Performance 3.9 3.6 3.4
Heat Pump Watts 450 655 860
Heat Pump Amperes 2.9 3.8 3.5
Weight (Net/Ship) 117/127 123/133 123/133
265V Models AZ65H07EAD AZ65H09EAD AZ65H12EAD AZ65H15EAD
Cooling BTUH 7,000 9,500 11,600 14,200
EER (BTU/Watt) 12.8 11.7 11.4 10.3
Dehumidification Pts/Hr 1.5 2.5 3.7 4.8
Refrigerant type R-410A R-410A R-410A R-410A
CFM, indoor fan high 360 420 410 400
CFM, indoor fan low 205 300 300 290
Vent CFM (full open)* 38 40 45 44
Power factor 95% 94% 97% 97%
Sensible heat ratio
@ 265 volts 77% 68% 62% 60%
Cooling Watts 545 810 1,015 1,375
Total Cooling Amperes, F.L. 2.2 3.3 4.1 5.5
Amperes, L.R. 11.7 16.5 23.5 29.0
Reverse cycle heat BTUH 6,200 8,100 10,000 13,300
Coefficient of Performance 3.9 3.5 3.4 3.2
Heat Pump Watts 460 670 850 1,210
Heat Pump Amperes 1.9 2.8 3.5 4.9
Weight (Net/Ship) 100/110 106/116 106/116 111/121
Listed by
Underwriters
Laboratories
AZ45 SERIES 265V
AZ65 SERIES 265V
265V Models AZ45E07EAC AZ45E09EAC AZ45E12EAC AZ45E15EAC
Cooling BTUH 7,100 9,500 11,500 14,700
EER (BTU/Watt) 13.2 11.6 11.7 10.5
Dehumidification Pts/Hr 1.64 2.7 3.5 4.6
Refrigerant type R-410A R-410A R-410A R-410A
CFM, indoor fan high 350 393 393 435
CFM, indoor fan low 220 260 290 330
Vent CFM (full open)* 33 38 38 47
Power factor 95% 94% 97% 97%
Sensible heat ratio
@ 265 volts 72% 67% 62% 63%
Cooling Watts 540 815 990 1,400
Total Cooling Amperes, F.L. 2.2 3.3 4.0 5.5
Amperes, L.R. 11.7 16.5 23.5 29.0
Weight (Net/Ship) 95/105 103/113 106/116 107/117
AZ45 series cooling with electric heat (Premium Guard Seacoast Protection)
AZ45 series cooling with electric heat (Dry Air 25)
AZ65 (typical) series heat pump with backup electric heat
(Premium Guard Seacoast Protection)
AZ65 series heat pump with backup electric heat
(Internal Condensate Removal)
AZ65 series heat pump with backup electric heat (Makeup Air)
ZONELINE
®
PACKAGED TERMINAL AIR CONDITIONERS SPECIFICATIONS
VISIT ZONELINE.COM OR CALL 888.231.2548