Architect and Engineering Manual

27
PREPARATION OF THE WALL SLEEVE FOR ALL 
TYPES OF CONSTRUCTION 
Do not remove the stiffener from inside the wall sleeve or 
the weather closure panel from the outside face of the wall 
sleeve until the outdoor grille and chassis are ready to be 
installed.
1. Position the wall sleeve into the wall. The room-side edge 
of the RAB71B or RAB78B wall sleeve should be at least 
flush with the finished wall for line-cord installations and 
permanent-connection installations when no sub-base 
is used, and should project into the room at least 2-3/8" 
when a sub-base is used. The outside edge of the wall 
sleeve should extend at least 1/4" beyond the outside wall. 
This is necessary for proper caulking, to prevent sealing 
the drain holes in the rear flange of the wall sleeve, and 
to facilitate the installation of an accessory drain, if used. 
If the minimum exterior dimensions are not met, refer to 
pages 32–33. 
  The wall sleeve should be level from side to side and  
from level to 1/4 bubble tilt to the outdoors. The 
condensate disposal system in the unit is designed 
to dissipate the condensate water generated during 
cooling operation in accordance with AHRI standards 
and actually uses this water for maximum unit 
efficiency. A level unit will also ensure proper  
drainage from the RAD10 drain kit to a building 
internal drain and proper performance of the Internal 
Condensate Removal (ICR) system optional on heat 
pump units. 
2. The wall sleeve should be secured to the wall at both 
sides. Use a minimum of two screws or other fastening 
device on each side. (See Figure 2 on page 28.) Mark the 
wall sleeve on each side 2" from the bottom and 2" from 
the top at a point where basic wall structure is located. 
Drill wall sleeve and use fasteners appropriate for wall 
construction. All holes for fasteners in the side of the 
wall sleeve must be at least 2" up from the bottom of the 
wall sleeve. Never locate screws or put other holes in the 
bottom of the wall sleeve. The only exception is when an 
RAD10 drain kit is installed to connect to an internal drain 
system. (See page 37 for RAD10 drain kit information.)
    If the wall opening is greater than the sleeve dimensions, 
spacers must be used on the sides between the wall 
sleeve and the wall support structure to prevent 
distorting the wall sleeve.
3. Caulk or gasket the entire opening on the outside 
between the wall sleeve and exterior wall surface (four 
sides) to provide total water and air seal. 
4. Caulk or gasket room-side opening between wall sleeve 
and interior wall surface (four sides). Openings beneath 
or around the wall sleeve can allow outdoor air to leak 
into the room, resulting in increased operating costs and 
improper room temperature control.
Care should be taken in location of electrical supply 
entry in relationship to wall sleeve to assure access  
to receptacle or junction box once unit is installed. 
•  Refer to page 45 for maximum power cord length. 
•   Permanently connected units close to finished floor  
must allow for conduit clearance.
SLEEVE ANGLES 
In some installations, such as curtain walls, window walls, 
or where the structural material of the wall is insufficient 
to support or fasten wall sleeve, sleeve angles may be 
used. Sleeve angles are pieces of steel or other material of 
similar structural strength that are formed to a 90° angle, 
with holes to fasten the sleeve angle to the wall sleeve 
and to the structural component of the wall surrounding 
the wall sleeve.
The following describes the procedure when field-
fabricated and -installed sleeve angles are applied. 
1. Position sleeve angles around top and sides of wall 
sleeve at the desired location. Position sleeve angles 
vertically on each side of wall sleeve to provide a level 
installation. 
2. Mark wall sleeve through holes in sleeve angles. The 
lowest hole on the sides of the wall sleeve must be a 
minimum of 2" above the bottom of the sleeve.
3. For RAB71B wall sleeve, drill 5/32" diameter holes 
at locations marked on wall sleeve in Step 2, and 
assemble angles to wall sleeve using #10 x 1/2" self-
tapping screws. For RAB78B wall sleeve, follow the 
same procedure except use a #10 x 1/2" bolt, washer 
and nut to attach sleeve angles to sleeve. Install screws 
or bolts from inside  
wall sleeve. 
4. Do not drill any holes in bottom of wall sleeve.  
Do not distort wall sleeve. 
5. Do not use sleeve angles for a lintel.
WALL SLEEVE INSTALLATION DATA (CONTINUED)
ARCHITECTS & ENGINEERS DATA MANUAL AZ45/AZ65 SERIES










