Architect and Engineering Manual

25
of 250 volts be “permanently connected.” There are also 
some installations where units connected to voltage 
sources under 250 volts may also need to be “permanently 
connected.” If you are in doubt about the requirements 
for a particular installation, consult Article 440 of the NEC 
or the local electrical inspector. These requirements are 
designed to protect personal safety and should be strictly 
followed. Although NEC is cited here as a reference, all 
electrical wiring and installations must conform to any  
and all local electrical codes and regulations.
“Permanent connection” generally means wiring to the 
unit must be contained in an enclosed “chaseway,” where 
access to the wiring connections is more restrictive 
than a normal line cord plugged into a receptacle. NEC 
requirements may be met by using flexible or rigid conduit 
to contain the wiring between the unit and a junction 
box that contains the wiring connections. The conduit 
is connected to the unit and to the junction box with 
connectors to hold the conduit in place. The junction  
box may be located in the floor or the wall of the structure, 
but only approved connectors may be used outside the 
unit or the junction box. The sub-base is UL
®
 listed as a 
junction box for permanent connection of a Zoneline unit.
Using a sub-base in an installation requiring permanent 
connection provides a convenient, consistent location  
for unit wiring to be connected to building wiring. The use  
of a sub-base is not required, but the convenience and the 
improved aesthetics it offers make the use of a sub-base  
a viable means of permanent connection.
RAK204U — The RAK204U Series of sub-base provides 
a design that fits the site needs and is available for use 
with Zoneline PTAC/PTHP units. The RAK204U will most 
likely be used for support of the wall sleeve and unit. The 
RAK204U is the same physically as the other sub-bases 
except there is no receptacle installed. Receptacles and 
wiring can be field installed and, by using the RAK205CW 
chaseway and the RAK4002D junction box, perform 
the same function as any of the other sub-base kits by 
selecting the correct receptacle and installing it in the 
interior mounting plate inside the RAK204U.
230/208-volt receptacles can also be mounted in the 
cover plate for easy access when direct-connect wiring 
is not required. 265-volt units are to be “Permanently 
(or Direct) Connected” and the external receptacle 
(when wiring is not enclosed in a chaseway) does not 
meet this requirement. A knockout for a fuseholder  
or a disconnect is also provided in the cover plate. 
The 230/208-volt sub-bases include a short, sub-base 
power connection kit. Since sub-base connected units 
are not considered to be line-cord connected, a Leakage 
Current Detection Interrupter or Arc Fault Current 
Interrupter device is not necessary. 
RAK204D15C 208/230-volt 15-amp receptacle. Receptacle 
is NEMA6-20R with 18" of #12AWG wires attached to the 
receptacle. Short power connection kit included. Chaseway 
included.
RAK204D20C 208/230-volt 20-amp receptacle. 
Receptacle is NEMA6-20R with 18" of #12AWG wires 
attached to the receptacle. Short power connection kit 
included. Chaseway included.
RAK204D30C 208/230 volt 30-amp receptacle. 
Receptacle is NEMA6-30R with 18" of #12AWG wires 
attached to the receptacle. Short power connection kit 
included. Chaseway included.
The junction box (RAK4002D for AZ45 and AZ65 
Series units) that mounts on the chassis of 230/208-
volt sub-base connected units must be purchased 
separately.  
SUB-BASES FOR THE 265-VOLT UNITS: 
RAK204E15C 265-volt 15-amp receptacle.  
Receptacle is NEMA7-15R with 18" of #12AWG wires 
attached to the receptacle. Chaseway and 3’ Power 
Connection Kit included.
RAK204E20C 265-volt 20-amp receptacle.  
Receptacle is NEMA7-20R with 18" of #12AWG wires 
attached to the receptacle. Chaseway and 3’ Power 
Connection Kit included.
RAK204E30C 265-volt 30-amp receptacle.  
Receptacle is NEMA7-30R with 18" of #12AWG wires 
attached to the receptacle. Chaseway and 3’ Power 
Connection Kit included.
The junction box for 265-volt units is shipped with the 
chassis since all 265-volt units are to be “permanently  
(or direct) connected.”
There are separate internal compartments to permit 
separation of low-voltage (Class 2) connections from  
line-voltage connections as required by National Electrical 
Code (NEC). Conduit containing building wiring enters 
the sub-base through knockouts located in the rear or 
bottom of the sub-base and is not accessible when the 
wall sleeve is installed.
The sub-base attaches to the RAB71B wall sleeve with 
two clips (field-assembled) that are screwed into field-
drilled holes in the bottom front flange of the wall sleeve. 
It attaches to the RAB78B wall sleeve with clips that fit 
over molded ribs without requiring the use of screws into 
the wall sleeve. (See page 35 for illustration.) Since the 
sub-base extends under the wall sleeve, clearance from 
the inner edge of the wall sleeve to the finished wall must 
be 2-3/8" or greater. The sub-base has four leveling legs 
and adjustable side channels to enable the area under the 
wall sleeve to be enclosed. Clearance from the bottom 
edge of the wall sleeve to the finished floor must be 
between 3" and 5".
The sub-base may be used as support for the chassis and 
wall sleeve in installations where the wall is of insufficient 
thickness to provide secure mounting of the wall sleeve.
WALL SLEEVE INSTALLATION DATA (CONTINUED)
ARCHITECTS & ENGINEERS DATA MANUAL AZ45/AZ65 SERIES










