Architect and Engineering Manual

17
In many installations, control of the operation of the unit 
at a location remote from the unit itself is desired. A unit 
mounted high in the wall or over a door, for instance, 
where the unit-mounted controls are inaccessible, can 
be connected to a wall-mounted thermostat. Other 
installations may use remote thermostat control for design 
or performance enhancement. The unit is connected to 
the thermostat by low-voltage wiring which permits the 
operation of the unit to be selected and the temperature 
sensed at the thermostat. 
Important Notes: Remote thermostat wiring should  
not be run through the wall sleeve. Thermostat wiring 
should exit the wall below the unit and enter the unit 
between room cabinet and chassis. Wire molding may  
be used to hide thermostat wiring. If a sub-base is  
used, the thermostat wiring may be concealed by the  
sub-base. Thermostat wiring should not be run parallel  
to line voltage wires since induced current may cause 
erratic operation. 
All Zoneline
®
 AZ45 and AZ65 Series units are adaptable to 
Class 2 remote low-voltage thermostats. The only additional 
field-supplied components are the remote thermostat and 
wiring necessary to connect it.
The controls on the unit are not functional when the remote 
control function is used. 
CONTROL PANEL 
 USE WALL THERMOSTAT 
  —will illuminate whenever any 
  button on the unit controls is 
  pressed if the unit is set up to 
  be controlled by a remote wall 
  thermostat. The LED will dim 
  down after a few seconds and 
then turn off after a few minutes as to not disturb the guest 
in a dark room.
RESISTANCE HEAT MODELS
The Zoneline AZ45 series resistance heat units may be 
connected to a single-stage thermostat designed for use 
with cooling with electric heat systems. GE Appliances 
offers four thermostats compatible with the  
AZ45 Series unit. 
RAK149P2*  
Digital programmable thermostat 
with one fan speed works with 
single-stage or two-stage heating 
systems. Requires five connection 
wires for AZ45 series. 
RAK180W1*  
Energy management occupancy sensing  
wireless thermostat.
Note: Set Aux mode 6 to “A” mode for 
Autochangeover thermostat. See page 15.
*NOTE: Default setup of unit is as a two-stage heating system and 
 must be changed to single stage for use with the AZ45 series.
RAK149F2*  
Digital thermostat with two 
fan speeds that works with 
single-stage or two-stage heating 
systems. Requires six connection 
wires for AZ45 series. 
The remote thermostat-Class 2 option (Mode 6 in the  
auxiliary control setting) must be turned ON to enable  
remote thermostat control. Refer to installation 
instructions packaged with the chassis. 
Please see page 51 for installation recommendations  
for the remote thermostat wiring. Compatibility 
of other thermostats considered for use with GE 
Appliances Zoneline units is the responsibility of  
the customer. 
The control voltage on the remote control conductors is 
24-volts AC. The AC voltage may not be compatible with 
some solid-state thermostats. 
If using a 1-fan speed remote thermostat, the fan speed 
for the AZ45 Series in remote thermostat operation 
is selected by the connection of the fan wire from the 
thermostat to either the HIGH or LOW wire on the remote 
thermostat connector. See the sketch of the connector 
below for the color of the HIGH and LOW fan-speed wire. 
Operating the unit in low fan speed reduces the operating 
sound level of the unit and increases dehumidification of 
the room.
Freeze Sentinel and Heat Sentinel remain operational if 
the unit is connected to a remote thermostat. The unit 
may be connected to a Central Desk Control (CDC) 
system and controlled with a remote thermostat when 
the CDC system has the unit in operation. See page 16 
for additional information on the CDC system.
Unit temperature-limiting settings are not functional  
when unit is connected to a remote thermostat.
NOTE: The low voltage transformer which powers  
the remote thermostat (and other controls) is  
“self-recovering” from potential wiring shorts. Should 
you lose low voltage control power (to the thermostat 
and the display panel on the unit), remove power to  
the unit, check the thermostat wiring for shorts, 
correct the issue and reapply power to the unit. 
NOTE: With the new AZ45 and AZ65 Series, 
thermostat twinning is allowed, where more than 
one unit may be connected to a single remote 
thermostat. In order to accomplish this, ONLY ONE 
POWER SOURCE (24VAC – R TERMINAL WIRE) CAN 
BE CONNECTED TO THE THERMOSTAT. All other 
thermostat wires of the additional unit should be 
connected as directed. 
THERMOSTAT WIRING DIAGRAM
Black -C- Common 
White -W- AUXHeat 
Yellow -Y-Compressor 
Blue -not used 
on AZ45 Series 
Green -GH- HighFan 
Tan -GL- LowFan 
Red -R- 24VAC 
Zoneline Thermostat 
Connector 
REMOTE THERMOSTAT CONTROL










