Sales Guide

15
SUB-BASE
MODEL VOLTAGE AMPS RECEPTACLE
RAK204U N/A N/A N/A
RAK204D15P 230/208 15 NEMA6-20R
RAK204D20P 230/208 20 NEMA6-20R
RAK204D30P 230/208 30 NEMA6-30R
RAK204E15 265 15 NEMA7-15R
RAK204E20 265 20 NEMA7-20R
RAK204E30 265 30 NEMA7-30R
230/208 Volt sub-bases include appropriate power cord kit.
265 Volt units are to be direct connected. Cordset through enclosed chaseway into interior
sub-base receptacle meets the NEC requirements.
Tandem
230/208V 15 Amp
NEMA6-15R
Perpendicular
230/208V 20 Amp
NEMA6-20R
Large tandem
230/208V 30 Amp
NEMA6-30R
265V 15 Amp
NEMA7-15R
265V 20 Amp
NEMA7-20R;
receptacle used
on 265V sub-base
GE0720-3
265V 30 Amp
NEMA7-30R;
receptacle used
on 265V sub-base
GE073
RECEPTACLES/SUB-BASES
POWER CONNECTION KITS ARE REQUIRED ON ALL ZONELINE CHASSIS (SEE CHART BELOW).
The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of
connecting the unit to the building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the
unit is to be permanently connected, a permanent connection kit would be used. 265 volt cord set units must be installed
in compliance with National Electrical Code.
®
Power connection kits
Required on all models. See specification sheet
for heater KW and branch circuit ampacity.
RAK3153A/3203A/3303A
230/208 volt line cord
connection kit
RAK4157/4207/4307
230/208 volt universal
power supply kit
RAK5157/5207/5307
265 volt universal power
supply kit
230/208 VOLT LINE CORD CONNECTED UNITS
LCDI Power
Connection Kit RAK3153A RAK3203A RAK3303A
Heater KW 2.4/2.32 3.3/3.2 4.7/4.53
Watts 2,400/2,320 3,300/3,200 4,700/4,530*
BTUH 8,150/7,900 11,200/10,900 16,000/15,450
Amps 11.0/11.6 15.1/16.0 21.2/22.4
Min. circuit amps 15 20 30
Recommended
protective device
15 amp time delay
fuse or breaker
20 amp time delay
fuse or breaker
30 amp time delay
fuse or breaker
265 VOLT PERMANENT CONNECTED UNITS** (CORD SET)
RAK5172 RAK5202 RAK5302
2.4 3.4 4.8
2,400 3,400 4,800*
8,150 11,550 16,350
9.6 13.3 18.6
15 20 30
15 amp time delay
fuse or breaker
20 amp time delay
fuse or breaker
30 amp time delay
fuse or breaker
265 VOLT DIRECT CONNECTION KIT
RAK5157 RAK5207 RAK5307
2.4 3.4 4.8
2,400 3,400 4,800*
8,150 11,550 16,350
9.6 13.3 18.6
15 20 30
15 amp time delay
fuse or breaker
20 amp time delay
fuse or breaker
30 amp time delay
fuse or breaker
230/208 VOLT DIRECT CONNECTION KIT
RAK4157 RAK4207 RAK4307
Heater KW 2.4/2.32 3.3/3.2 4.7/4.53
Watts 2,400/2,320 3,300/3,200 4,700/4,530*
BTUH 8,150/7,900 11,200/10,900 16,000/15,450
Amps 11.0/11.6 15.1/16.0 21.2/22.4
Min. circuit amps 15 20 30
Recommended
protective device
15 amp time delay
fuse or breaker
20 amp time delay
fuse or breaker
30 amp time delay
fuse or breaker
*Wattage not available with 7,000 BTU systems
**To be used with sub-base
†To be used with sub-base or connection to building wiring.
Specifications subject to change.