Installation Guide
• ASTM E2112-01* and AAMA 2400-02* recom-
mend the use of a minimum 9 inch wide flashing
membrane beyond the rough opening.
• Grace recommends a 12 inch wide flashing mem-
brane for proper waterproofing of the window
sill, providing a drainage plane in the rough open-
ing.
• Remove any weather-resistive barrier from sill
area prior to membrane installation for full adhe-
sion of the membrane to the structural sill.
• Refer to “Table I – Flashing Lengths and Cut
Formulas,” (page 8), to determine appropriate
flashing lengths.
• After the membrane has been installed, roll firmly into place.
• Install membrane such that all laps shed water (following the
shingle principle). Always work from the low point to the high
point.
• Mechanically fasten the membrane at vertical terminations, as
necessary.
• Weather-resistive barrier refers to housewrap, building paper/
felt, Perm-A-Barrier
®
, etc.
• Windows/siding should be installed according to the standards
set by the window/siding manufacturers and/or respective
organizations.
• Apply Grace Vycor Self-Adhered Flashings only in fair weather
when the air, surface and membrane temperatures are at a
minimum of -4°C (25°F). For temperatures below 5°C (40°F),
keep material warm until use. (Refer to Technical Letter 3.)
• Install directly onto a clean, dry and frost-free surface.
Remove dust, dirt and debris. Surfaces shall be smooth and
continuous without voids, damaged or unsupported areas.
• Priming is generally not required for most substrates pro-
vided they are clean and dry. However, on concrete,
masonry and DensGlass Gold
®
, apply Perm-A-Barrier WB
Primer at a coverage rate of 6-8 m
2
/L (250-350 ft
2
/gal).
If adhesion is found to be marginal, also prime wood
composition and gypsum sheathing with Perm-A-Barrier
WB Primer at the same coverage rate.
*
Standard Practice for Installations of Exterior Windows,
Doors and Skylights.
**
Standard Practice for Installations of Windows with a
Mounting Flange in Stud Frame Construction.
How to Apply Grace Vycor Self-Adhered Flashing Tapes
PRE-INSTALLATION NOTES
Flashing Location Flashing Lengths and Cut Formulas
Sill Flashing Rough opening width + (2 x flashing width)
Jamb Flashing Rough opening height + (2 x flashing width) – 1 inch
Head Flashing Rough opening width + (2 x flashing width) + 2 inch
Example for 9 inch wide flashing
If rough opening width = 30 inches
If rough opening height = 50 inches
For Sill: 30 inches + (2 x 9 inches) = 48 inches
For Jamb: 50 inches + (2 x 9 inches) – 1 inch = 67 inches
For Head: 30 inches + (2 x 9 inches) + 2 inches = 50 inches
This table will assist in determining the pre-cut flashing
lengths required to properly install window flashing
(as per ASTM E2112-01).
TABLE I – Flashing Lengths
and Cut Formulas
8
7
Refer to our web sites for further product information.
www.graceconstruction.com and www.graceathome.com