Please refer to the local regulations to determine the system wire size, types
and temperatures.
The cross section of the cables and the capacity of the connectors must be
selected to suit the maximum system short circuit current (The
recommended section area for a single piece of Module is 4 mm, and the
recommended rated current for the connector is greater than 10A),
otherwise the cables and connectors shall be overheated under large
current. Caution: The maximal temperature of the cable is 85
C while the
upper limited temperature of the connector is 105
C .
Make sure the electric components such as the connectors and inverters are
o-state during the installation.
To reduce lightning damage, the loop area should be kept as small as
possible when laying cables. It is recommended to use fuses in each string.
When connected in series, the maximum number of the Modules are determined by
the system design, inverter type and environment. ( shown in Figure 6).
When connected in parallel, the current output is equal to the sum of each string’s
current ( shown in Figure 7). Fuse is necessary for each module string. Please take
reference to the local regulation. Recommended maximum parallel Modules
congurations: Fuse rating/Isc+1.
Figure 6 Figure 7