Logic HE Balanced Flue Log Installation User Instructions

18
2. Rear Flue
2
Terminal dimensions:
395 x 200 x 200 mm (H x W x D)
Guard supplied
Cut to length as required on site.
2.1 Decide on the terminal position.
2.2 Measure the height from the finished hearth level/ base of
the appliance to the centre of the required hole.
2.3 A masonry installation requires the addition of a suitable
lintel to support the opening. Refer to Installation
Instructions, Technical Information for details of the flue
length.
NOTE - Carefully consider:
a) Terminal positions
b) Flue supports
c) Weatherproofing
d) Fire precautions
For all the above options, you must conform to local and
national codes of practice.
2.4 Use only Gazco supplied flue on this appliance.
2.5 A guard (supplied) must be fitted to any terminal less than 2
metres above any access such as level ground, a balcony or
above a flat roof.
Timber Framed Buildings
2.6 It will be necessary to provide additional clearance when the
flue passes through a wall containing any combustible
materials so as to prevent a fire hazard.
2.7 The hole through which the flue will pass, must have a steel
sleeve which is positioned so that an air gap of at least
25mm is maintained between the outer surface of the flue,
and any part of the sleeve.
2.8 For further guidance on the installation of gas appliances in
timber framed buildings, contact your local buildings control
authority.
Installation Instructions
Site Requirements
3. Gas Supply
3.1 Before installation, ensure that the local distribution
conditions (identification of the type of gas and pressure)
and the adjustment of the appliance are compatible.
3.2 Ensure the gas supply delivers the required amount of gas
and is in accordance with the rules in force.
3.3 Factory-sheathed/wrapped soft copper tubing with small
ridges which allow pipe movement are considered to be a
suitable alternative to a pipe sleeve, when recessing the unit
into a cavity wall the gas supply is best fed through the wall
from the outside. Soft soldered joints can only be used
outside the appliance.
3.4 This appliance is supplied complete with a factory fitted
isolation device incorporated into the inlet connection. No
further isolation device is therefore required.
4. Ventilation
4.1 This appliance requires no additional ventilation.