Riva2 600 Balanced Flue Installation Instructions
12
Installation Instructions
Model Gas
CAT.
Gas Type Working
Pressure
Aeration Injector Gas Rate
m
3
/h
Input kW
(Gross)
Country
High Low
Riva2 600
I
2H
Natural Gas
G20
20mbar 2 x 6.5 mm Ø 410 0.610 6.4 4.4 GB, IE
Riva2 600
I
3P
Propane G31 37mbar N/A 200 0.252 6.7 4.4 GB, IE
Efciency Class 1 - 92% / NO
x
Class 4
Flue Outlet Size Ø 100mm
Flue Inlet Size Ø 152mm Ø
Gas Inlet Connection Size Ø 8mm
Technical Specification
Covering the following models:
RESTRICTOR REQUIREMENT - VERTICAL & HORIZONTAL FLUE SPECIFICATION
Riva2 600 - Nat Gas
Vertical ue height from top of appliance Horizontal length Restrictor size
500mm - 999mm Up to 1000mm N/A
1000mm - 1499mm Up to 3000mm N/A
1500mm - 3000mm Up to 3499mm 70mm
1500mm - 3000mm 3500mm - 6000mm N/A
RESTRICTOR REQUIREMENT - VERTICAL & HORIZONTAL FLUE SPECIFICATION
Riva2 600 - LPG
Vertical ue height from top of appliance Horizontal length Restrictor size
500mm - 999mm Up to 1000mm N/A
1000mm - 1499mm Up to 3000mm N/A
1500mm - 2499mm Up to 2999mm 70mm
1500mm - 2499mm 3000mm - 6000mm N/A
2500mm - 3000mm Up to 2499mm 60mm
2500mm - 3000mm 2500mm - 3499mm 70mm
2500mm - 3000mm 3500mm 6000mm N/A
TOP EXIT - VERTICAL ONLY INCLUDING OFFSET
Riva2 600 - Nat Gas
Vertical ue height from top of appliance Restrictor size
1500mm - 2999mm 52mm
3000mm - 10000mm 47mm
TOP EXIT - VERTICAL ONLY INCLUDING OFFSET
Riva2 600 - LPG
Vertical ue height from top of appliance Restrictor size
2000mm - 2999mm 52mm
3000mm - 10000mm 47mm
Riva2 600
Nat Gas
Riva2 600
LPG
134-134 134-702