Riva2 600 600HL Conventional Flue Installation Instructions

20
Installation Instructions
6a. Edge Finish Installation
6a.1 This method is designed so that non-combustible board can
be taken right up to the edge of the flange of the appliance.
6a.2 Build the studwork chimney breast and enclosures to the
desired size to include the protected platform at the
required height.
Ensure that the minimum 50mm distance to combustible
studwork is maintained.
6a.3 Line the aperture for the appliance with 12mm thick
non-combustible material as shown, see Diagram 16.
Non-combustible board used to protect the studwork can
line the aperture inside the 150mm clearance distance, see
Diagram 16.
16
6a.4 Site the appliance and decide on flue requirements.
6a.5 Prepare the flue connection using the chosen method
described in Section 2 ensuring that distances to
combustible materials are maintained at all times.
Connect the flue and install the appliance into the aperture.
At the same time ensure that the elbow and supply pipe
passes through the silicon panel at the back of the
appliance.
Do not secure the appliance at this time.
6a.6 Fit non-combustible board to the studwork around the
aperture. This should extend a minimum of 400mm above
the appliance and at least 150mm to the sides of the
appliance, see Diagram 17 and Diagram 18.
17
Min 400mm
Bottom of Appliance
Min 150mm
Min 150mm
18
Non-combustible
Board
Appliance
Outer
Casing
Appliance
Edge
150mm
Clearance
Combustible
Studs
Plasterboard
Appliance Flange
Ensure the clearances are maintained, see Diagram 15.
6a.7 Apply plasterboard to the remainder of the studwork.
6a.8 Fix the self adhesive foam seal around the back of the fixing
flange of the appliance.
6a.9 Secure the appliance to the non-combustible board through
the 6 fixing holes, using the anchor fixings provided, see
Diagram 19 & 20.
19