Riva2 600 600HL Conventional Flue Installation Instructions

14
Installation Instructions
1. Flue & Chimney Requirements
WHEN INSTALLING A FLUE SYSTEM PLEASE REFER
TO THE MANUFACTURER’S INSTRUCTIONS.
The European chimney standards now describe chimneys
and flues by their temperature, pressure and resistance to
corrosion, condensation and fire. To identify the correct flue
system, the minimum flue specification is shown in the
Technical Specification. Existing chimneys are not covered
by this system.
The flue must be installed in accordance with all local and
national regulations and the current rules in force:
1.1 The chimney or flue system must comply with the rules in
force, and must be 127mm (5") in diameter.
1.2 A flexible liner must be continuous from the appliance spigot
to the roof terminal.
1.3 The minimum effective height of the flue must be 3m (10').
1.4 The flue must be free from any obstruction.
1.5 Any damper plates must be removed or secured in the fully
open position and no restrictor plates fitted.
1.6 The chimney should be swept immediately before installing
the appliance, but it need not be swept if you can see the
chimney is clean and free from obstruction throughout.
2. Flue Options
There are three main suitable Conventional Flues:
Top Exit - Builders Opening Lined
127mm (5”)
Rear Exit - Builders Opening Unlined
178m (7”) minimum
Stud work is Top Exit only - Rigid Twin Wall Flue Pipe
127mm (5”)
3. Gas Supply
This appliance is intended for use on a gas installation with a
governed meter.
3.1 Make sure local distribution conditions (identification of the
type of gas and pressure) and the adjustment of the
appliance are compatible before installation.
3.2 Ensure the gas supply delivers the required amount of gas
and is in accordance with the rules in force.
3.3 Soft copper tubing can be used on the installation and soft
soldered joints outside the appliance and below the firebed.
3.4 A factory fitted isolation device is part of the inlet
connection; no further isolation device is required.
3.5 All supply gas pipes must be purged of any debris that may
have entered prior to connection to the appliance.
3.6 The gas supply enters through the silicone panel located on
the LEFT-HAND side on the rear of the outer box. Slit with a
sharp knife prior to passing the supply pipe through.
3.7 The gas supply must be installed in a way that does not
restrict the removal of the appliance for servicing and
inspection.
4. Ventilation
IMPORTANT: Ensure any national ventilation
requirements are taken into account during installation
of the appliance.
UK ONLY:
The appliance has a nominal input not exceeding 7.0kW
(net) and does not normally require any additional
permanent ventilation.
If however, spillage is detected when commissioning the
appliance, there may be insufficient natural ventilation and
additional ventilation may be required.
FOR THE REPUBLIC OF IRELAND REFER TO THE
RULES IN FORCE FOR VENTILATION REQUIREMENTS.
5. Appliance Location
If fitting this appliance with a decorative frame it
cannot be installed with the base of the appliance less
than 150mm from the floor level. The frame requires a
minimum clearance to allow air to circulate.
If this appliance is fitted less than 150mm from the
floor, then it will require a hearth to protect the floor.
The hearth should have a minimum dimension of
12mm thick, projecting 300mm in front and 150mm
either side of the appliance.
5.1
The minimum opening dimensions are shown in Diagram 1.
1
DIMENSION Riva2 600 Riva2 600HL
A 674mm 671mm
B 350mm 350mm
C 564mm 793mm
Site Requirements