Logic HE Range Conventional Flue Log Effect Installation User Instructions
33
Fault Finding Charts
Red Indicator Meaning
Permanently Lit
Valve tried to light but failed and
in LOCKOUT E00
Flashing very fast
Valve is busy (will not accept any
command)
Flashing once a second Valve detects an error
Flashing once every 10 seconds
Indication of low battery power
in valve
Flashing twice every 10 seconds
(handset only)
Indication of low battery power in
handset and valve
Permanently off
Valve in standby or in a stable
operation
On momentarily after power up Valve doing a self test
Appears after pressing start
Indicates time to release pressing
the start button
If the valve indicates an error:
Allow the appliance to cool (if hot).
Check the battery status and replace with new if in any doubt.
Electronic Control Valve Fault Analysis
Servicing Instructions
Reset the error by rst pressing the power button (with the
appliance cool).
Press once again to start the re.
If the error repeats refer to the error code table below.
Error Code Meaning
E00 Valve Locked due to failed ignition.
E01 Indicates that possibly the content of CO is too
high in ambient atmosphere.
E02 Ambient temperature around Gas valve in the
re too hot (exceeded 72°C).
E03 Thermocouple connection to valve issue.
Incorrect reading from thermocouple.
E04 Flame detected on pilot after valve has
shutdown.
E05 Flame detected on pilot before valve has
started.
E06 & 07 Occurs when supply voltage is too low to
operate the valve.
E24 Occurs when thermocouple does not reach its
nal temperature within 1 minute.