Logic HE Range Conventional Flue Log Effect Installation User Instructions

17
Installation Instructions
Site Requirements
1. Flue & Chimney Requirements
1.1 The chimney or flue system must comply with the rules
inforce, and must be a minimum of 125mm (5”) in diameter.
The appliance can also be fitted into a LFE type (non
recessed) metal flue box with a 5” (125mm) diameter
prefabricated metal flue system or flexible liner. Refer to
Diagram 1, Pre Fab Metal Box for dimensions.
* Class 1 flues. Chimneys over 9" x 9" must be lined.
1.2 The minimum effective height of the flue or chimney must be
3 m (10ft).
1.3 The chimney or flue must be free from any obstruction. Any
damper plates should be removed or secured in the fully
open position, and no restrictor plates should be fitted.
1.4 The chimney should be swept immediately before installing
the appliance, but it need not be swept if you can see the
chimney is clean and free from obstruction throughout.
1.5 Ensure that there is a smooth taper transition from the
fireplace opening into the chimney or flue.
1.6 The flue pull should be checked prior to installation of the
appliance. Apply a smoke pellet to the flue or chimney
opening and ensure that the smoke is drawn into the
opening. If there is not a definite flow, preheat the chimney
for a few minutes and re-test the flow.
IF THERE IS STILL NO DEFINITE FLOW, THE CHIMNEY
MAY REQUIRE ATTENTION - SEEK EXPERT ADVICE.
2. Appliance Location
2.1 This appliance must stand on a non combustible hearth that
is at least 12mm thick. If the appliance is greater than 50mm
above the floor, then no hearth is required, although due
consideration should be given to how the heat may affect
the floor material.
2.2 NOTE: It is recommended you construct the back panel
of the fireplace from natural materials cut into three
or more sections to prevent cracking. Resin-based
materials may not be suitable. This appliance is an
effective heat producer and attention must be paid to
the construction and finish of the fireplace.
2.3 These appliances must be hearth mounted into a into a non-
combustible opening to National Standards. The minimum
dimensions shall be as shown in Diagram 1.
A
B
G
D
F
C
E
1
Flue Type
Dimension
Brick Built
Class 1
Pre Fab Metal
Box
A 410 407
B 560 560
C 350 300
D 300 300
E 150 150
F 710 707
G - 600