Logic HE Balanced Flue Log Installation User Instructions
19
5. Appliance Location
NOTE: It is recommended you construct the back panel
of the fireplace from natural materials cut into three or
more sections to prevent cracking. Resin-based
materials may not be suitable. This appliance is an
effective heat producer and attention must be paid to
the construction and finish of the fireplace.
5.1 This appliance must stand on a non-combustible hearth that
is at least 12mm thick.
5.2 It must be fitted into a non-combustible opening. The
minimum dimensions shall be as shown in Diagram 3.
A
B
D
F
C
E
3
Dimensions Min Max
A 420mm 450mm
B 560mm 575mm
C 230mm -
D 300mm -
E 150mm -
F 720mm 750mm
5.3 These appliances must be hearth mounted into a fireplace
opening conforming to National Standards.
5.4 If the appliance is greater than 50mm above the floor, then
no hearth is required, although due consideration should be
given to how the heat may affect the floor material.
5.5 This appliance can only be installed on an outside wall with
suitable clearances for the flue terminal and guard (if
required).
5.6 This appliance is not suitable for installation into a
combustible wall. All combustible material must be removed
from the area shown, see Diagram 5.
720
420
150
560
300
860
5
5.7 The maximum depth of combustible shelf is 150mm at a
minimum height of 300mm above the fireplace opening.
Installation Instructions
Site Requirements