Reflex 75T Multi Sided Balanced Flue Installation Manual
45
IGNITION LEAD
Unplug the Ignition lead from the control box.
Ignition Lead
Carefully cut cable ties from the vidaflex and disconnect the lead
from the electrode.
IMPORTANT Ensure not to cut the cables.
GAS VALVE
To change the gas valve:
Remove the Log Burners and Main Control Assembly.
Disconnect the Gas Inlet Pipe, Arrow A.
Disconnect the Gas Outlet Pipe, Arrow B.
Disconnect the Pilot Pipe, Arrow C.
Disconnect the Thermocouple, Thermocurrent Wires and the
Interrupter Block, Arrow D.
Remove the Eight Wire Loom, Arrow E.
There is an access hole abovce the cable plug oin the valve.
Insert a small screwdriver to release the locking tab.
C
D
A
B
E
Screw
Screw
Remove the 2 screws securing the Valve to the support bracket and
withdraw the Valve.
Replace in reverse order and check for leaks.
MAGNETIC SAFETY VALVE
Remove the Log Burners and Main Control Assembly.
Undo the Thermocouple from the Interrupter Block and remove the
2 Interrupter Leads.
Unscrew the Interrupter Block from the back of the Valve.
Undo the silver Magnetic Valve retaining nut on the back of the
Valve.
Gently tap out the Mag Valve.
Replace with a new unit.
Reassemble in reverse order ensuring that the interrupter leads are
connected correctly with the blue tag lead furthest away from the
gas valve body.
Check for leaks.
CONTROL BOX
To replace the Control Box first remove the Main Control Assembly.
Cut the cable tie holding the Ignition lead and the Thermocurrent
cables.
Disconnect the Wi-Fi lead (if fitted), Module lead, and Solenoid
lead from the Control Box.
Wi-Fi Lead
Solenoid
Lead
Module
Lead
8-Way Cable
Remove the Ignition Lead. The Control Box is held on by Velcro
pads.
Remove the 2 screws to remove the 2 Interrupter Leads.
SERVICING INSTRUCTIONS