Reflex 75T Multi Sided Balanced Flue Installation Manual

12
INSTALLATION INSTRUCTIONS
TOP FLUE VERTICAL OFFSET
KIT (8530/8530AN)
Used with kit 8524. A minimum rise of 500mm (191/2) is required to
the rst bend.
OPTIONAL EXTRA FLUE LENGTHS
AND BENDS
All ue components are 150mm diameter (6")
NOMINAL
LENGTH
ACTUAL
LENGTH
STAINLESS
FINISH
ANTHRACITE
FINISH
200mm 140mm 8527 8527AN
500mm 440mm 8528 8528AN
1000mm 940mm 8529 8529AN
45° Bend N/A 8507 8507AN
90° Bend N/A 8508 8508AN
NOTE: The following areas need careful consideration.
a) Terminal positions
b) Flue supports
c) Weatherproong
d) Fire precautions
For all the above options, local and national codes of practice
must be adhered to.
IMPORTANT:
1M VERTICAL, TERMINAL AND STRAIGHT FLUE
LENGTHS MUST NOT BE CUT!
REMOVING THE MOUNTING BRACKET
This appliance weighs 108Kg. The manufacturer
has designed this appliance to attach to a masonry
wall and all xings supplied reect this. However
if desired it is possible to locate the Reex on a
non-combustible studwork wall providing it is
constructed to give adequate load baring support.
I
f intending to install the appliance on a studwork
wall it is essential that the battens are located
across the xing areas of the wall mounting
bracket.
23mm
300mm
846mm
27mm
155mm
227mm
71mm
430mm
430mm
825mm
135mm
784mm
691mm
228mm
228mm
390mm
323mm
200mm
FLUE OPTIONS