Reflex 75T Balanced Flue User Installation Manual
53
THERMOCOUPLE
5
IGNITION LEAD
1
Carefully cut cable ties from the vidaflex and disconnect the lead
from the electrode.
IMPORTANT Ensure not to cut the cable.
GAS VALVE
C
D
A
B
E
Screw
Screw
1
To change the gas valve:
Disconnect the Gas Inlet Pipe, Arrow A.
Disconnect the Gas Outlet Pipe, Arrow B.
Disconnect the Pilot Pipe, Arrow C.
Disconnect the Thermocouple, Thermocurrent Wires and the
Interrupter Block, Arrow D.
Remove the Eight Wire Loom, Arrow E.
There is an access hole in the top of the Control Bracket to release
the locking tab.
Remove the 2 screws securing the Valve to the support bracket and
withdraw the Valve.
Replace in reverse order and check for leaks.
MAGNETIC SAFETY VALVE
Undo the Thermocouple from the Interrupter Block and remove the
2 Interrupter Leads.
Unscrew the Interrupter Block from the back of the Valve.
Undo the silver Magnetic Valve retaining nut on the back of the
Valve.
Gently tap out the Mag Valve.
Replace with a new unit.
Reassemble in reverse order ensuring that the interrupter leads are
connected correctly with the blue tag lead furthest away from the
gas valve body.
Check for leaks.