Reflex 75T Balanced Flue User Installation Manual
19
TOP FLUE UP AND OUT
WITH ADDITIONAL BEND
Any additional bend may be used on the horizontal section (either
45° or 90°), but the overall horizontal ue run will be reduced.
When A = 1.0 to 1.499 metres B + C = 1.0 metres maximum
When A = 1.499 metres to 3.0 metres B + C = 4.0 metres maximum
EITHER 45˚
OR 90˚
TOP FLUE VERTICAL KIT
(8524)
This ue is vertical from the top of the appliance. A minimum
vertical rise of 1.5m (4’9”) to a maximum of 10m (32’10”).
The basic kit comprises:
2 x 1m lengths
1 x 1m terminal lengths
1 x 52mm restrictor
1 x 47mm restrictor
1 x 60mm restrictor
1 x 70mm restrictor
Extra lengths may be added from the table.
TOP FLUE VERTICAL OFFSET
KIT (8530/8530AN)
Used with kit 8524. A minimum rise of 500mm is required to the rst
bend.
FLUE OPTIONS