Reflex 105 Multi-Sided Installation Instructions 1
32
ENCLOSURE CONSTRUCTION
2 SIDED INSTALLATION
VENTILATION
Note: If the lower section of the enclosure is sealed
(to the oor or capped if designed as a oating
shelf) it will be necessary to provide a vent with a
free area of 150cm
2
on each side.
If the upper section is sealed (to the ceiling or
capped if designed as a oating shelf) it will be
necessary to provide a vent with a free area of
400cm
2
on each side.
Gazco recommend building the enclosure from the following
materials:
Metal Studwork
Non-combustible board:
Masterboard or Promafour - NOT PINK BOARD
Heart Resistant Plaster: Purimacho (any spider cracks that develop
after installation will need to be rubbed down and relled with
Purimacho heat resistant ller to stablise).
Ensure all distances to combustible materials are maintained.
Example enclosure
6. Upper Front Panel
5. Lower Front Panel
3. Open
Side Panel
7. Front
Side Panel
8. Short
Side
Panel
4. Lower Base Panel
2. Shadow Gap Panels
- See minimum housing clearance requirements
1. Closed Side Panel
(If not installing
against a wall)
F