Reflex 105 Multi-Sided Installation Instructions 1
27
ENCLOSURE CONSTRUCTION
3 SIDED INSTALLATION
VENTILATION
Note: If the lower section of the enclosure is sealed
(to the oor or capped if designed as a oating
shelf) it will be necessary to provide a vent with a
free area of 150cm
2
on each side.
If the upper section is sealed (to the ceiling or
capped if designed as a oating shelf) it will be
necessary to provide a vent with a free area of
400cm
2
on each side.
Gazco recommend building the enclosure from the following
materials:
Metal Studwork
Non-combustible board:
Masterboard or Promafour - NOT PINK BOARD
Heat Resistant Plaster: Purimacho (any spider cracks that develop
after installation will need to be rubbed down and relled with
Purimacho heat resistant ller to stablise).
Ensure all distances to combustible materials are maintained.
Example enclosure
1. Side Panel
3. Side Panel
6. Upper Front
Panel
5. Lower Front
Panel
8. Inner
Side
Panel
4. Base Panel
2. Shadow Gap Panels
- See minimum housing
clearance requirements
7. Inner
Side
Panel