Commissioning
1. Commissioning
1.1 Check the ame picture, log layout.
1.2 Check the gas pressure.
1.3 Close all door and windows in the room.
1.4 Ignite the appliance and operate on maximum for 5 minutes.
1.5 Position a lighted smoke match near the top of the draught
diverter opening (under the canopy) and angle towards the
ue. Check all smoke is drawn in along the opening, see
Diagram 1.
1
Canopy
If there is any doubt:
1.6 Run the appliance for a further 10 minutes and repeat the
test.
If there are any extractor fans in the room or adjacent
rooms, the test must be repeated with the fans running on
maximum.
IF SPILLAGE PERSISTS, DISCONNECT THE APPLIANCE
AND SEEK EXPERT ADVICE.
1.7 Complete the Commissioning Checklist at the front of this
manual covering:
— Thermocouple soundness checks.
This is to include ensuring the thermocouple is secure on
the pilot bracket assembly, lead connection and integrity.
— Flue checks
— Gas checks.
— Log/fuel effect layout - ame picture.
For working pressure test, refer to Installation Instructions
Section 8.
1.8 Upon completion of the commissioning and testing of the
installation and correct operation of the appliance, the
installer must instruct the user how to operate the appliance.
1.9 Guide the user through the User Instructions paying
particular attention to:
a) Regular servicing (Section 7 of the User Instructions).
b) Ventilation (Section 8 of the User Instructions) - point out
the ventilation positions where applicable.
c) Hot surfaces (Section 10 of the User Instructions).
d) How the appliance works with the remote control
handset and the modes of operation (Section 2 of the User
Instructions).
e) How to change settings in the auto mode and program
modes of operation.
f) What to do if the appliance fails to operate (Section 11 of
the User Instructions).
For future reference, record the installation details on the
Commissioning Sheet on page 3.
2. Reprogramming handset/Control box
2.1 To access the control box see Servicing Instructions, Section
4 - Removing the Log Burners and Main Control Assembly.
2.2 Press and hold the reset button on the control box until you
hear two signals. After the second longer signal:
2.3 Release the reset button and within 20 seconds:
2.4 Press the DOWN button on the handset until you hear two
additional short signals conrming the new code is set. If
there is a single long signal the code learning sequence has
failed or the wiring is incorrect.
Note: When pressing the DOWN button on the handset if
two beeps are not heard:
2.5 Release the DOWN button and CONN will be displayed
on the handset screen. An 8 second count will start on the
handset screen followed by two short beeps conrming the
new code is set. If there is a single long signal the code
learning sequence has failed or the wiring is incorrect.