Reflex 105 Conventional Flue User Installation Manual
19
Installation Instructions
5a.6 Secure the appliance through the 6 xing holes using the
screws provided, see Diagram 14.
14
5a.7 Build the chimney breast up to coincide with the edge,
allowing for the front to be skimmed level.
5a.8 Fit non-combustible board to the chimney breast around the
appliance, using the distance to combustibles detailed in
Diagram 15.
15
Min
400mm
Bottom of
Appliance
Min 200mmMin 200mm
5a.9 Fit plasterboard to the remaining of the chimney breast
front.
5a.10 Apply a heat resistant plaster around the appliance using
the distance to combustibles detailed in Diagram 15.
5a.11 Apply a plaster nish to remaining chimney breast front.
5a.12 If installing a decorative surround or front refer to separate
installation instructions.
The subframe for the decorative front can now be tted by
following the instructions supplied with the Front.
NOTE: THE SUBFRAME MUST SIT FLUSH TO THE
WALL LEVEL WITH THE APPLIANCE FLANGE.
6. Studwork Installation
6.1 DISTANCE TO COMBUSTIBLE MATERIAL
COMBUSTIBLE PARTS OF THE STUDWORK MUST BE
KEPT BEYOND THE MINIMUM DIMENSIONS SHOWN IN
DIAGRAM 16.
PROTECT THE NEAREST STUDWORK WITH NON-
COMBUSTIBLE MATERIAL AND MAINTAIN THESE
DIMENSIONS AT ALL TIMES, SEE DIAGRAM 16.
MINIMUM
COMBUSTIBLE
MATERIAL
CLEARANCES
16
400mm
100mm
150mm
12mm
100mm
200mm
200mm
200mm
12 mm
Non-combustible
board
12mm
Non-combustible
board
6.2 DO NOT PACK THE VOID AROUND OR ABOVE THE
APPLIANCE WITH INSULATION MATERIALS SUCH AS
MINERAL WOOL.
6.3 THE VOID BUILT FOR THE CASSETTE MUST BE
VENTILATED TO PREVENT A BUILD-UP OF HEAT.
VENTS MUST BE FITTED AT BOTH HIGH AND LOW
LEVELS OF A MINIMUM OF 200CM² EACH. THESE
VENTS MUST TAKE COLD AIR FROM THE ROOM AND
RETURN WARM AIR BACK INTO THE ROOM.
17
75mm