Reflex 105 Balanced Flue User Installation Manual

17
Site Requirements
IMPORTANT: REAR FLUE INSTALLATION
When fitting the appliance with a rear flue terminal
it is essential to observe distances to combustible
material when flue passes through a combustible
wall. Ensure the terminal is suitable protected if
fitting to an external combustible structure. There is
a fixing kit available from Gazco (Part No 999-220).
DO NOT INSTALL DIRECTLY ONTO A
COMBUSTIBLE SURFACE.
2.3 Decide on the terminal position.
2.4 Measure the height from the finished hearth level/ base of
the appliance to the centre of the required hole.
2.5 A masonry installation requires the addition of a suitable
lintel to support the opening. Refer to Installation
Instructions, Technical Information for details of the flue
length.
NOTE - Carefully consider:
a) Terminal positions
b) Flue supports
c) Weatherproofing
d) Fire precautions
For all the above options, you must conform to local and
national codes of practice.
2.6 Use only Gazco supplied flue on this appliance.
2.7 A guard (supplied) must be fitted to any terminal less than 2
metres above any access such as level ground, a balcony
or above a flat roof.
Timber Framed Buildings
2.8 It will be necessary to provide additional clearance when
the flue passes through a wall containing any combustible
materials so as to prevent a fire hazard.
2.9 The hole through which the flue will pass, must have a
steel sleeve which is positioned so that an air gap of at
least 25mm is maintained between the outer surface of the
flue, and any part of the sleeve.
2.10 For further guidance on the installation of gas appliances in
timber framed buildings, contact your local buildings control
authority.
2C. Top Flue Vertical Kit
(8524/8524AN)
2.11 This ue is vertical from the top of the appliance, see
Diagram 2d. A minimum vertical rise of 3m (9’10”) to a
maximum of 10m (32’10”). The basic kit comprises:
2 x 1m Lengths
1 x 1m Terminal lengths
1 x 52mm Restrictor
1 x 47mm Restrictor
1 x 60mm Restrictor
1 x 70mm Restrictor
Extra lengths may be added from the table in Section 3.
2e
2d. Top Flue Vertical Oset
Kit (8530/8530AN)
2.12 Used with kit 8534. A minimum rise of 500mm (191/2) is
required to the rst bend, see Diagram 2e.