Conventional Flue
15
Installation Instructions
Site Requirements
5.4 The non-combustible hearth must be at least 12mm thick,
and project a minimum of 50mm from the base of the
appliance in all directions.
5.5 The appliance is not suitable for installation against a
combustible wall. A combustible side wall must be a
minimum of 150mm (Vogue Midi / Midi Midline) or 200mm
(Vogue Midi T Midi/ Midi T Midline / Midi T Highline) from the
appliance.
5.6 This appliance can be installed with an up and out ue
(vertical wall - horizontal ue) or with a vertical ue with
roof termination (see Flue Options, Section 2 Site
Requirements).
NOTE: It is not recommended to install Midline/
Highline models on a bench.
HEARTH INSTALLATION
(NOT APPLICABLE FOR MIDLINE & HIGHLINE MODELS)
5.7 Building Regulations state this appliance must stand on
a non-combustible hearth that is at least 12mm thick and
projects 50mm minimum from the base of the appliance in all
directions, however Gazco recommend the hearth extends to
the following dimensions, see Diagram 2.
C
A
B
2
Dimensions Vogue Midi Vogue Midi T
A 716mm 716mm
B 498mm 467mm
C 12mm 12mm
MIDLINE & HIGHLINE MODELS
5.8 It is not necessary to site these products on a non-
combustible floor. However, for practical reasons, the floor
should be flat and solid to allow the appliance to be levelled
and secured in place.
5.9 This appliance may be situated anywhere in the room, but
due consideration should be taken to ensure that it is sited
within the constraints of the allowable flue configuration.
DO NOT INSTALL APPLIANCE ON A CARPET.
MINIMUM CLEARANCE
5.10 The appliance is not suitable for installation against a
combustible wall.
5.11
Ensure that all minimum clearances to combustible
materials are complied with as shown in Diagrams 3 & 4.
The specied clearances provide the minimum distance to
combustible materials. If the appliance is intended to be
installed into a non-combustible opening the clearance to the
sides and above the appliance can be reduced. However, it
is recommended that the specied clearances are maintained
irrespective of the materials used in the construction of the
opening to allow adequate air ow and access to controls.
The clearance at the rear of the appliance must always be
a minimum of 50mm.
A
B
A
3
D
C
4
Dimension
Vogue Midi /
Vogue Midi Midline
Vogue Midi T Midi/
Vogue Midi T Midline/
Vogue Midi T Highline
A 150 200
B 225 225
C 150 200
D 50 50
5.12 The above dimensions provide adequate clearance to
combustible materials. It may be necessary to add additional
clearance so that spillage tests can be performed when
necessary.