Balanced Flue
17
Installation Instructions
Site Requirements
3c. Top Flue Up and Out
with Additional Bend
3.12 An additional bend can be used on the horizontal section
(45° or 90°) but the overall horizontal ue is reduced, see
Diagram 4.
When A = 1.0 to 1.499 metres B+C = 1.0 metre max (Nat Gas - No restrictor,
LPG - 75mm Restrictor)
When A = 1.499 to 3.0 metres B+C = 4.0 metres max (Nat Gas - 70mm restrictor,
LPG - No restrictor)
4
EITHER 45˚
OR 90˚
3d. Top Flue Vertical Kit
3.13 This ue is vertical from the top of the appliance, see
Diagram 5. A minimum vertical rise of 2m (6’6”) to a
maximum of 10m (32’10”).
999-539/999-539AN - Vogue Midi/ Midline Models
The basic kit comprises:
2 x 1m lengths
1 x 1m terminal lengths
1 x 52mm restrictor (sliding plate assembly)
1 x 47mm restrictor (sliding plate assembly)
8524/8524AN - Vogue Midi/ Midline/ Highline T Models
The basic kit comprises:
2 x 1m lengths
1 x 1m terminal length
1 x 52mm restrictor
1 x 47mm restrictor - Not used on this appliance
1 x 60mm restrictor
1 x 70mm restrictor - Not used on this appliance
All Models
3.14 Extra lengths can be added, see Diagram 5.
3.15 Refer to Installation Instructions, Technical Specication to
identify when to use a restrictor.
5
2.0m
MIN
0.5m
MIN
10.0m
MIN
0.25m
2.5m
3e. Top Flue Vertical Offset Kit
(8530/8530AN)
3.16 Used with kit 999-539. A minimum rise of 500mm (19½) is
required to the rst bend, see Diagram 5.