Balanced Flue

16
3. Rear Flue
3.1 This ue extends horizontally from the back of the appliance,
see Diagram 2.
ALL MODELS (8526)
200mm min
550mm max
2
Terminal dimensions:
395 x 200 x 200 mm (H x W x D)
Guard supplied
Cut to length as required on site, see Diagram 2.
There are two types of ue terminal: horizontal (Section 3b)
and vertical (Section 3d).
3a. Top Flue Up and Out Kit
3.2 This ue rises vertically from the top of the appliance, then
continues horizontally outward, see Diagrams 3A & 3B.
The basic kit comprises:
ALL MODELS (8523/8523AN)
1 x 500mm vertical length
1 x 500mm terminal length
1 x 90 degree elbow
1 x wall plate
1 x 52mm restrictor
1 x 60mm restrictor
1 x 75mm restrictor
4 x xing screw
3A
Vogue Midi/ Midline
Installation Instructions
Site Requirements
3B
Vogue Midi T/ Midline/ Highline
3.3 This kit provides the minimum materials. Extra lengths can
be added to the vertical and horizontal sections; refer to
Section 4.
3.4 Refer to Installation Instructions, Technical Specication on
page 14 to identify when to use a restrictor.
3b. For horizontal terminal
installations:
3.5 Decide on the terminal position.
3.6 Measure the height from the top of the appliance to the
centre of the required hole. For minimum and maximum
dimensions see Diagram 3 & 4.
3.7 To t the ue you must have access to the top or the side of
the appliance to connect the ue.
3.8 Assemble the vertical sections making sure the top plate and
ue collar are tted before the ue pipe.
3.9 Add the 90° elbow.
3.10 Add the horizontal section and terminal. Only the
horizontal terminal can be reduced in size.
3.11 A masonry installation requires the addition of a suitable
lintel to support the opening. Refer to Installation
Instructions, Technical Information for details of the ue
length.