Conventional Flue

15
Installation Instructions
MINIMUM CLEARANCE
5.8 The appliance is not suitable for installation against a
combustible wall.
5.9
Ensure that all minimum clearances to combustible
materials are complied with as shown in Diagrams 3 & 4.
The specied clearances provide the minimum distance to
combustible materials. If the appliance is intended to be
installed into a non-combustible opening the clearance to the
sides and above the appliance can be reduced. However, it
is recommended that the specied clearances are maintained
irrespective of the materials used in the construction of the
opening to allow adequate air ow and access to controls.
The clearance at the rear of the appliance must always be
a minimum of 50mm.
A
B
A
3
D
C
4
Dimension Loft
A 200
B 225
C 200
D 50
5.10 The above dimensions provide adequate clearance to
combustible materials. It may be necessary to add additional
clearance so that spillage tests can be performed when
necessary.
Site Requirements