Balanced Flue

17
Installation Instructions
Site Requirements
5. Gas Supply
This appliance is intended for use on a gas installation with a
governed meter.
5.1 Before installation, ensure that the local distribution
conditions (identication of the type of gas and pressure) and
the adjustment of the appliance are compatible.
5.2 Ensure the gas supply delivers the required amount of gas
and is in accordance with the rules in force.
5.3 You can use soft copper tubing on the installation and soft
soldered joints outside the appliance and below the re.
5.4 A factory tted isolation device is part of the inlet connection;
no further isolation device is required.
5.5 All supply gas pipes must be purged of any debris that may
have entered prior to connection to the appliance.
5.6 The gas supply enters underneath the rear of the outer box:
5.7 The gas supply must be installed in a way that does not
restrict the removal of the appliance for servicing and
inspection.
6. Ventilation
6.1 This appliance requires no additional ventilation.
7. Appliance Location
7.1 Once the position of the appliance has been decided:
Follow the instructions for securing the appliance on Page 19.
7.2 The non-combustible hearth must be at least 12mm thick,
and project a minimum of 50mm from the base of the
appliance in all directions.
7.3 The appliance is not suitable for installation against a
combustible wall. See table on page 18 for minimum
distances to combustible materials.
This does not apply to wall mounted models.
7.4 This appliance can be installed with an up and out ue
(vertical wall - horizontal ue) or with a vertical ue with
roof termination (see Flue Options, Section 2 Site
Requirements).
HEARTH INSTALLATION
(NOT APPLICABLE FOR BASE SECTION INSTALLATIONS
MODELS)
7.5 Building Regulations state this appliance must stand on
a non-combustible hearth that is at least 12mm thick and
projects 50mm minimum from the base of the appliance in all
directions, however Gazco recommend the hearth extends to
the following dimensions, see Diagram 6.
C
A
B
6
Dimensions A B C
All Models 716mm 498mm 12mm
BASE SECTION INSTALLATION
7.6 It is not necessary to site these products on a non-
combustible floor. However, for practical reasons, the floor
should be flat and solid to allow the appliance to be levelled
and secured in place.
7.7 This appliance may be situated anywhere in the room, but
due consideration should be taken to ensure that it is sited
within the constraints of the allowable flue configuration.
DO NOT INSTALL APPLIANCE ON A CARPET.
SECURING THE APPLIANCE TO THE WALL
(WALL MOUNTED MODELS ONLY)
WARNING: This appliance weighs 62kg.
The manufacturer has designed this appliance to
attach to a masonry wall and all xings supplied
reect this. If siting on a studwork wall, the xing
points must be through the timber stud and not
plasterboard. Use appropriate xings.
DO NOT attach solely to a plasterboard wall.