Section 7: Sizing Tables and Pressure Drop Charts
7.2 CSST Capacity Tables - Natural Gas - Elevated Pressure
Table 7-9
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 1.0 PSI and a Pressure Drop of 13.0"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 261 181 146 125 111 101 87 77 70 65 60 57 53 48 43
18 1/2" 655 465 381 330 296 271 235 210 192 178 167 157 149 134 122
23 3/4" 1122 816 677 594 536 493 432 390 358 334 314 297 283 256 235
31 1" 2769 1984 1633 1422 1277 1170 1019 916 839 779 730 690 656 589 540
37 1-1/4" 4304 3064 2511 2181 1955 1788 1553 1392 1273 1180 1105 1043 991 888 812
48 1-1/2" 9134 6491 5316 4613 4133 3778 3279 2937 2685 2489 2330 2199 2087 1870 1709
60 2" 20768 14530 11790 10165 9061 8249 7112 6339 5771 5330 4976 4683 4435 3953 3599
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 37 33 30 26 23 21 19 18 17 16 15 14 14 13 13
18 1/2" 106 95 87 75 67 62 57 54 50 48 46 44 42 41 39
23 3/4" 206 186 171 150 135 124 116 109 103 98 94 91 87 84 82
31 1" 470 422 387 337 303 277 258 241 228 217 207 199 191 185 179
37 1-1/4" 705 632 578 502 450 412 382 357 337 320 306 293 282 272 263
48 1-1/2" 1484 1329 1215 1054 945 863 800 749 707 671 640 614 590 569 550
60 2" 3103 2766 2518 2171 1935 1762 1627 1519 1429 1354 1289 1232 1183 1138 1099
Table 7-10
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 2.0 PSI and a Pressure Drop of 1.0 PSI
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 392 271 219 188 167 152 130 116 105 97 90 85 80 71 65
18 1/2" 957 679 556 483 432 395 343 307 281 260 243 230 218 195 179
23 3/4" 1596 1161 964 844 762 701 614 554 510 475 447 423 403 364 335
31 1" 4004 2869 2361 2056 1847 1692 1474 1324 1213 1126 1056 998 949 852 781
37 1-1/4" 6269 4463 3658 3177 2848 2604 2262 2027 1854 1719 1610 1520 1443 1294 1183
48 1-1/2" 13331 9474 7758 6733 6032 5514 4785 4287 3918 3632 3401 3209 3047 2729 2495
60 2" 30841 21577 17508 15096 13456 12249 10561 9414 8570 7915 7389 6954 6586 5871 5344
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 56 49 45 39 34 31 29 27 25 24 23 22 21 20 19
18 1/2" 155 139 127 110 99 90 83 78 74 70 67 64 62 59 57
23 3/4" 293 265 243 213 193 177 165 155 147 140 134 129 124 120 116
31 1" 680 611 560 487 438 401 372 349 330 314 300 287 277 267 258
37 1-1/4" 1027 921 842 731 656 600 556 521 491 467 445 427 410 396 383
48 1-1/2" 2165 1940 1773 1539 1379 1260 1168 1094 1032 980 935 896 861 830 802
60 2" 4608 4107 3739 3224 2874 2616 2416 2255 2123 2010 1914 1830 1756 1690 1631
Caution: Capacities shown in the elevated pressure tables may exceed the capacity of the line regulator. Refer to Section 4 for Regulator
Capacities and Pressure Drops
Tables include losses for four 90° bends and two end fittings. Tubing runs with a larger number of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L=1.3n where L is additional length of tubing and n is the number of
additional fittings and/or bends.