Section 7: Sizing Tables and Pressure Drop Charts
Table 7-5
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 3.0"WC
Line Regulator Outlet (8 in.WC ) (based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 120 83 67 58 51 47 40 36 32 30 28 26 25 22 20
18 1/2" 318 226 185 160 144 131 114 102 93 86 81 76 72 65 59
23 3/4" 572 416 345 303 273 251 220 199 183 170 160 152 145 130 120
31 1" 1368 981 807 703 631 578 504 452 415 385 361 341 324 291 267
37 1-1/4" 2097 1493 1224 1063 953 871 757 678 620 575 539 508 483 433 396
48 1-1/2" 4435 3152 2581 2240 2007 1834 1592 1426 1304 1208 1131 1068 1014 908 830
60 2" 9755 6825 5538 4775 4256 3874 3340 2978 2711 2504 2337 2199 2083 1857 1690
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 17 15 14 12 11 10 9 8 8 7 7 7 6 6 6
18 1/2" 51 46 42 37 33 30 28 26 24 23 22 21 20 20 19
23 3/4" 105 95 87 76 69 63 59 56 53 50 48 46 44 43 42
31 1" 232 209 191 167 150 137 127 119 113 107 102 98 95 91 88
37 1-1/4" 344 308 282 245 219 201 186 174 164 156 149 143 137 132 128
48 1-1/2" 720 645 590 512 459 419 389 364 343 326 311 298 286 276 267
60 2" 1457 1299 1183 1020 909 827 764 713 671 636 605 579 555 535 516
Table 7-6
Maximum Capacity of FlashShield™ Flexible Gas Piping in Cubic Feet Per Hour of Natural Gas
with a Gas Pressure of 0.5 PSI or Less and a Pressure Drop of 4.0"WC
(based on a 0.60 specific gravity gas)
Tubing Tubing Length (ft)
EHD Size 5 10 15 20 25 30 40 50 60 70 80 90 100 125 150
13 3/8" 140 97 78 67 60 54 47 41 38 35 32 30 29 25 23
18 1/2" 366 260 213 185 165 151 131 118 107 100 93 88 83 75 68
23 3/4" 653 475 394 345 312 287 251 227 209 194 183 173 165 149 137
31 1" 1571 1126 927 807 725 664 578 520 476 442 415 392 372 334 306
37 1-1/4" 2415 1719 1409 1224 1097 1003 871 781 714 662 620 585 556 498 456
48 1-1/2" 5110 3632 2974 2581 2312 2114 1834 1643 1502 1392 1304 1230 1168 1046 956
60 2" 11314 7915 6423 5538 4936 4493 3874 3453 3144 2904 2711 2551 2416 2154 1960
Tubing Tubing Length (ft)
EHD Size 200 250 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
13 3/8" 20 18 16 14 12 11 10 10 9 8 8 8 7 7 7
18 1/2" 59 53 49 42 38 34 32 30 28 27 26 24 24 23 22
23 3/4" 120 108 100 87 79 72 67 63 60 57 55 53 51 49 48
31 1" 267 240 220 191 172 157 146 137 130 123 118 113 109 105 101
37 1-1/4" 396 355 324 282 253 231 214 201 189 180 172 164 158 152 147
48 1-1/2" 830 744 680 590 528 483 448 419 396 376 358 343 330 318 308
60 2" 1690 1507 1372 1183 1054 960 886 827 779 737 702 671 644 620 598
Tables include losses for four 90° bends and two end fittings. Tubing runs with a larger number of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L=1.3n where L is additional length of tubing and n is the number of
additional fittings and/or bends.