Section 3: System Configuration
SIZING RUN “C”
Run “C” is sized by the load of the supplied appliances and the run length from the meter to the furthest appliance
e total load of the supplied appliances is 2 x (50 + 25 + 28) = 206CFH
e run length to the 4th floor Fireplace (furthest appliance) is 5 + 10 + 10 + 10 + 25 = 60ft
Referring to Table 7-23 (Rigid pipe 0.5"WC pressure drop): for a 60ft run, 1" pipe has a capacity over 206CFH
(actual: 260)
SIZING RUN “D”
Run “D” is sized by the load of the supplied appliances and the run length from the meter to the furthest appliance
e total load of the supplied appliances is 50 + 25 + 28 = 103CFH
e run length to the 4th floor Fireplace (furthest appliance) is 5 + 10 + 10 + 10 + 25 = 60ft
Referring to Table 7-23 (Rigid pipe 0.5"WC pressure drop): for a 60ft run, 3/4" pipe has a capacity over
103CFH (actual: 138)
Sizing Runs E1, F1, G1, E2, F2 and G2 are similar to the sizing of E3, F3 and G3.
SIZING RUN “E3”
Run “E3” is sized by the load of the supplied appliances and the run length from the meter to the supplied appliance
e load of the dryer is 28CFH
e run length to the dryer is 5 + 10 + 10 + 15 = 40ft
Referring to Table 7-4 (2"WC pressure drop) for a 40ft run, 3/8" CSST has a capacity of 28CFH (actual: 32)
SIZING RUN “F3”
Run “F3” is sized by the load of the supplied appliances and the run length from the meter to the supplied appliance
e load of the fireplace is 25CFH
e run length to the fireplace is 5 + 10 + 10 + 25 = 50ft
Referring to Table 7-4 (2"WC pressure drop) for a 50ft run, 3/8" CSST has a capacity 25CFH (Check against fireplace
sizing)
Referring to Table 4-6 (Fireplace Sizing), 1/2" CSST has a capacity over 25CFH (actual: 83)
Using the larger result, this run will be sized to 1/2" CSST
SIZING RUN “G3”
Run “G3” is sized by the load of the supplied appliances and the run length from the meter to the supplied appliance
e load of the water heater is 50CFH
e run length to the water heater is 5 + 10 + 10 + 15 = 40ft
Referring to Table 7-4 (2"WC pressure drop) for a 40ft run, 1/2" CSST has a capacity over 50CFH (actual: 93)
SIZING RUN “E4”
Run “E4” is sized by the load of the supplied appliances and the run length from the meter to the supplied appliance
e load of the dryer is 28CFH
e run length to the dryer is 5 + 10 + 10 + 10 + 15 = 50ft
Referring to Table 7-4 (2"WC pressure drop) for a 50ft run, 3/8" CSST has a capacity of 28CFH (actual: 29)