Brochure
Gastite Division, Titeflex Corporation
1116 Vaughn Parkway / Portland, TN 37148
800.662.0208 / www.gastite.com / gastite@gastite.com
36
April 2015
Section 3: System Configuration
SIZING RUN “B”
• Run “B” is sized by the total load of all supplied appliances and the section length
• e total load of the supplied appliances is 36 + 52 + 28 + 25 = 141CFH
• e section length is 5ft
• Referring to Table 7-21 (Pressure drop per foot for FlashShield™ CSST): for a 150CFH load, 1" CSST has a drop of 0.006"WC / ft
• e pressure drop over Run “B” is: 0.006" x 5ft = 0.030"WC
• e available pressure at the end of run “B” is 5.440"WC - 0.030"WC = 5.410"WC
SIZING RUN “C”
• Run “C” is sized by the total load of all supplied appliances and the section length
• e total load of the supplied appliances is 52 + 28 + 25 = 105CFH
• e section length is 10ft
• Referring to Table 7-21 (Pressure drop per foot for FlashShield™ CSST): for a 110CFH load, 1" CSST has a drop of 0.003"WC / ft
• e pressure drop over Run “C” is: 0.003" x 10ft = 0.030"WC
• e available pressure at the end of run “C” is 5.410"WC - 0.030"WC = 5.380"WC
SIZING RUN “D”
• Run “D” is sized by the total load of all supplied appliances and the section length
• e total load of the BBQ and the dryer is 25 + 28 = 53CFH
• e section length 10ft
• Referring to Table 7-21 (Pressure drop per foot for FlashShield™ CSST): for a 60CFH load, 3/4" CSST has a drop of 0.004"WC / ft
• e pressure drop over Run “D” is: 0.004" x 10ft = 0.040"WC
• e available pressure at the end of run “D” is 5.380"WC - 0.040"WC = 5.340"WC
SIZING RUN “E”
• Run “E” is sized by the load of the supplied appliance and the section length
• e load of the BBQ is 25CFH
• e section length is 5ft
• Referring to Table 7-21 (Pressure drop per foot for FlashShield™ CSST): for a 30CFH load, 1/2" CSST has a drop of 0.005"WC / ft
• e pressure drop over Run “E” is: 0.005" x 5ft = 0.025"WC
• e available pressure at the end of run “E” is 5.340"WC - 0.025"WC = 5.315"WC
SIZING RUN “F”
• Run “F” is sized by the load of the supplied appliance and the section length
• e load of the furnace is 80CFH
• e section length to the furnace is 10ft
• Referring to Table 7-21 (Pressure drop per foot for FlashShield™ CSST): for a 80CFH load, 3/4" CSST has a drop of 0.008"WC / ft
• e pressure drop over Run “F” is: 0.008" x 10ft = 0.080"WC
• e available pressure at the end of run “F” is 5.440"WC - 0.080"WC = 5.360"WC
SIZING RUN “G”
• Run “G” is sized by the load of the supplied appliance and the section length
• e load of the water heater is 36CFH
• e section length to the water heater is 10ft
• Referring to Table 7-21 (Pressure drop per foot for FlashShield™ CSST): for a 40CFH load, 1/2" CSST has a drop of 0.009"WC / ft
• e pressure drop over Run “G” is: 0.009" x 10ft = 0.090"WC
• e available pressure at the end of run “G” is 5.410"WC - 0.090"WC = 5.320"WC